26
Rockwell Automation Publication 1790-UM001B-EN-P - April 2021
Chapter 3 Module Data, Status, and Channel Configuration for Analog Input Modules
Analog Input Data File With Discrete Input Expansion Module
shows the structure for an analog base module with one of the
following 8-input modules:
•
1790-8BV8BX, 1790-T8BV8BX
•
1790-T8A0X discrete expansion module.
Table 10 - Word/Bit Description
Word
Decimal Bit
Description
Read Word 0
Bits 00…11
Channel 0 input data
Bits 12…15
Not used: Set to 0
Read Word 1
Bits 00…11
Channel 1 input data
Bits 12…15
Not used: Set to 0
Read Word 2
Bits 00…11
Channel 2 input data
Bits 12…15
Not used: Set to 0
Read Word 3
Bits 00…11
Channel 3 input data
Bits 12…15
Not used: Set to 0
Read Word 4
Bits 00…03
Status bits for individual channels — Bit 00 corresponds to input channel 0, bit
01 corresponds to input channel 1 and so on.
When set (1) indicates:
No field power
Open wire —
4…20 mA current input only
Under range —
4…20 mA current input only
Recoverable module fault (whole channel to be set)
Unrecoverable module fault (whole channel to be set)
Bits 04…15
Not used: Set to 0
Table 11 - 1790D-N4C0, 1790D-TN4C0, 1790D-TN4V0 Input Data File with 8-Bit Discrete
Expansion Module
Word
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Not Used
Analog Input Data Channel 0
1
Not Used
Analog Input Data Channel 1
2
Not Used
Analog Input Data Channel 2
3
Not Used
Analog Input Data Channel 3
4
Not Used
S3
S2
S1
S0
5
Not Used
D7
D6
D5
D4
D3
D2
D1
D0
Table 12 - Word/Bit Description
Word
Decimal Bit
Description
Read Word 0
Bits 00…11
Channel 0 input data
Bits 12…15
Not used: Set to 0
Read Word 1
Bits 00…11
Channel 1 input data
Bits 12…15
Not used: Set to 0
Read Word 2
Bits 00…11
Channel 2 input data
Bits 12…15
Not used: Set to 0
Read Word 3
Bits 00…11
Channel 3 input data
Bits 12…15