Chapter 9 Connected Components Workbench Software
4. Download the new settings to the safety light curtain.
5. Upload and confirm (lock) the new settings.
Process Details
Place only the fixed objects in the light curtain field. The object can be singular
or multiple fixed objects can be within the light curtain field. Mount the
Optical Interface Device onto the receiver. Connect the USB cable from
computer with the Connected Components Workbench software to the
Optical Interface Device. Turn on power to the light curtain.
starts the process by connection to the safety light curtain.
1. Click Connect to Device. Wait for the connection to be made. When the
connection is made, Diagnose becomes enabled, and Download and
Upload become disabled.
2. Click Blanking Settings. The Blanking configuration type is not relevant.
Figure 129 - Connect to Device
3.
shows the Blanking settings. Teach is enabled. Click Teach
Blanking Zones.
Figure 130 - Teach Blanking Zones
4.
shows the caution message that allows you to cancel if
necessary. After reading the message, click OK.
Figure 131 - Delete Current Settings