Installation Instructions

MicroLogix™ 1000 Programmable Controllers

Catalog Numbers 1761-L10BWA, -L10BWB, -L10BXB, -L16AWA, -L16BWA, 
-L16BWB, -L16BBB, -L16NWA, -L16NWB, -L20AWA-5A, -L20BWA-5A, 
-L20BWB-5A, -L32AAA, -L32AWA, -L32BWA, -L32BWB, -L32BBB

http://literature.rockwellautomation.com/idc/groups/literature/documents/in/
1761-in001_-mu-p.pdf

Cette publication est disponible en français sous forme électronique (fichier PDF). Pour la 
télécharger, rendez-vous sur la page Internet indiquée ci-dessus.

Questa pubblicazione è disponibile in Italiano in formato PDF. Per scaricarla collegarsi al sito 
Web indicato sopra.

Diese Publikation ist als PDF auf Deutsch verfügbar. Gehen Sie auf die oben genannte 
Web-Adresse, um nach der Publikation zu suchen und sie herunterzuladen.

Esta publicación está disponible en español como PDF. Diríjase a la dirección web indicada 
arriba para buscar y descarga esta publicación.

Esta publicação está disponível em portugués como PDF. Vá ao endereço web que aparece 
acima para encontrar e fazer download da publicação.

FR

IT

DE

ES

PT

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Summary of Contents for 1761-L10BWA

Page 1: ...ternet indiquée ci dessus Questa pubblicazione è disponibile in Italiano in formato PDF Per scaricarla collegarsi al sito Web indicato sopra Diese Publikation ist als PDF auf Deutsch verfügbar Gehen Sie auf die oben genannte Web Adresse um nach der Publikation zu suchen und sie herunterzuladen Esta publicación está disponible en español como PDF Diríjase a la dirección web indicada arriba para bus...

Page 2: ...efesotomasyon com Allen Bradley Rockwell plc servo drive ...

Page 3: ...L32BWB L32BBB Topic Page Important User Information 4 Overview 5 Catalog Number Detail 5 Related Publications 6 Safety Considerations 7 Physical Dimensions 9 Mounting Your Controller Horizontally 10 Wiring Your Controller 13 Grounding Your Controller 15 Surge Suppression 16 Sinking and Sourcing 19 Wiring Your Analog Channels 20 Specifications 21 efesotomasyon com Allen Bradley Rockwell plc servo d...

Page 4: ...s publication Allen Bradley publication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Allen Bradley office describes some important differences between solid state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication Reproductio...

Page 5: ...for the controller is composed of the following IMPORTANT Identifies information that is critical for successful application and understanding of the product 1761 L 20 A W A 5 A Analog I O Number of Analog I O 4 Inputs 1 Output Power Supply A 120 240V ac B 24V dc Output Type A Triac B 24V dc FET W Relay X Relay 24V dc FET Bulletin Number Controller Number of Digital I O Input Type A 120V ac B 24V ...

Page 6: ...ld Programmer HHP to monitor and develop control logic programs for the MicroLogix 1000 controller MicroLogix 1000 with Hand Held Programmer HHP User Manual 1761 6 2 More information on proper wiring and grounding techniques Industrial Automation Wiring and Grounding Guidelines 1770 4 1 The procedures necessary to install and connect the AIC and DNI Advanced Interface Converter AIC and DeviceNet I...

Page 7: ...onnect equipment unless power has been switched off and the area is known to be non hazardous Do not connect or disconnect connectors while circuit is live unless area is known to be non hazardous This product must be installed in an enclosure All cables connected to the product must remain in the enclosure or be protected by conduit or other means Environment Classification Communication Cable Cl...

Page 8: ...remplacer de composants ou déconnecter l équipement sans s être assuré que l alimentation est coupée et que l environnement est classé non dangereux Ne pas connecter ou déconnecter les connecteurs lorsque le circuit est alimenté à moins que l environnement ne soit classé non dangereux Ce produit doit être installé dans un boîtier Tous les câbles qui lui sont connectés doivent rester dans le boîtie...

Page 9: ...ntally mounted Controller 1761 Length mm in Depth mm in Height mm in L10BWA 120 4 72 73 2 87 80 3 15 L16BWA L16NWA L16AWA 133 5 24 L20AWA 5A 200 7 87 L20BWA 5A L32AWA L32BWA L32AAA L10BWB 120 4 72 40 1 57 L10BXB L16BBB L16BWB L16NWB L20BWB 5A 200 7 87 L32BBB L32BWB B A B A A Greater than or equal to 50 8 mm 2 in B Greater than or equal to 50 8 mm 2 in Top Bottom Side Side Side efesotomasyon com Al...

Page 10: ... spacing requirements Refer to the mounting template from the back of this document 2 Hook the top slot over the DIN rail 3 While pressing the controller against the rail snap the controller into position 4 Leave the protective wrap attached until you are finished wiring the controller ATTENTION Be careful of metal chips when drilling mounting holes for your controller Drilled fragments that fall ...

Page 11: ...e your controller is spaced properly 3 Drill holes through the template 4 Remove the mounting template 5 Mount the controller 6 Leave the protective wrap attached until you are finished wiring the controller Mounting Your Controller Vertically Your controller can also be mounted vertically within an enclosure using mounting screws or a DIN rail To insure the stability of your controller we recomme...

Page 12: ...rature 0 C to 40 C 32 F to 113 F 1 Operating Shock Panel mounted 9 0g peak acceleration 11 1 ms duration 3 times each direction each axis Operating Shock DIN rail mounted 7 0g peak acceleration 11 1 ms duration 3 times each direction each axis 1 DC input voltage derated linearly from 30 C 30V to 26 4V A Greater than or equal to 50 8 mm 2 in Top Side Bottom Side efesotomasyon com Allen Bradley Rock...

Page 13: ... 2 wire maximum per terminal screw Solid 14 to 22 AWG Stranded 16 to 22 AWG IMPORTANT The diameter of the terminal screw head is 5 5 mm 0 220 in The input and output terminals of the MicroLogix 1000 controller are designed for the following spade lugs Call out Dimension C 6 35 mm 0 250 in E 10 95 mm 0 431 in maximum L 14 63 mm 0 576 in W 6 35 0 250 in X 3 56 mm 0 140 in C X 9 91 mm 0 390 in maximu...

Page 14: ...f the controller IMPORTANT Be careful when stripping wires Wire fragments that fall into the controller could cause damage Remove the protective wrap after wiring your controller Failure to remove the wrap may cause the controller to overheat IMPORTANT This symbol denotes a functional earth ground terminal which provides a low impedance path between electrical circuits and earth for non safety pur...

Page 15: ...he Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 ATTENTION All devices connected to the user 24V power supply or to the RS 232 channel must be referenced to chassis ground or floating Failure to follow this procedure may result in property damage or personal injury Chassis ground user 24V ground and the RS 232 ground are internally connected You must connect the chassi...

Page 16: ... life of the output circuits You also reduce the effects of radiated voltage transients and prevent electrical noise from radiating into system wiring and facility The following diagram shows an output with a suppression device We recommend that you locate the suppression device as close as possible to the load device If you connect a micro controller FET output to an inductive load we recommend t...

Page 17: ... a micro controller triac output to control an inductive load we recommend that you use varistors to suppress noise Choose a varistor that is appropriate for the application The suppressors we recommend for triac outputs when switching 120V ac inductive loads are a Harris MOV part number V175 LA10A or an Allen Bradley MOV catalog number 599 K04 or 599 KA04 Consult the varistor manufacturer s data ...

Page 18: ... not use with triac outputs Bulletin 709 Motor Starter 120V ac 1401 N10 Bulletin 700 Type R RM Relays ac coil None Required Bulletin 700 Type R Relay Bulletin 700 Type RM Relay 12V dc 12V dc 199 FSMA9 Bulletin 700 Type R Relay Bulletin 700 Type RM Relay 24V dc 24V dc 199 FSMA9 Bulletin 700 Type R Relay Bulletin 700 Type RM Relay 48V dc 48V dc 199 FSMA9 Bulletin 700 Type R Relay Bulletin 700 Type R...

Page 19: ...ng The input energizes when low level voltage is applied to the input terminal active low Connect the power supply VDC to the corresponding DC COM terminal I 9 I 10 DC COM I 0 I 1 I 2 I 3 I 4 I 5 I 6 I 7 I 8 I 11 I 12 I 13 I 14 I 15 I 16 I 17 I 18 I 19 DC COM 14 30 VDC DC OUT 24V VDC for Sourcing VDC for Sourcing VDC for Sinking VDC for Sinking Sinking Inputs Sourcing Inputs I 9 I 10 DC COM I 0 I ...

Page 20: ...es the transmitter specifications as shown below VAC VDC O 4 O 5 O 6 NOT USED O 7 I 10 I 11 IA IA 3 I IA 2 I IA SHD IA 1 V IA SHD IA 0 V IA OA OA 0 I OA 0 V OA SHD Sensor 1 V Voltage Sensor 2 V Voltage Sensor 3 I Current Sensor 4 I Current meter You can configure either voltage or current output operation Jumper unused inputs or IA 0 3 IA IA 0 3 IA GND IA 0 3 IA Transmitter Transmitter Transmitter...

Page 21: ...perly grounded use Belden cable 8761 for wiring the analog channels making sure that the drain wire and foil shield are properly earth grounded route the Belden cable separate from any ac wiring Additional noise immunity can be obtained by routing the cables in grounded conduit Grounding Your Analog Cable Use shielded communication cable Belden 8761 The Belden cable has two signal wires black and ...

Page 22: ...32 VA 33 VA 36 VA 22 VA 24V dc Not Applicable 5W 7W Power Supply Max Inrush Current 30A for 8 ms 30A for 4 ms 24V dc Sensor Power V dc at mA Not Applicable 200 mA Not Applicable Max Capacitive Load User 24V dc 200 µF Power Cycles 50 000 minimum Vibration Operating 5 Hz to 2k Hz 0 381 mm 0 015 in peak to peak 2 5g panel mounted 1 1hr per axis Non operating 5 Hz to 2k Hz 0 762 mm 0 030 in peak to pe...

Page 23: ...peak to peak 5g 1hr per axis 1 DIN rail mounted controller is 1g Shock 2 2 Refer to page 12 for vertical mounting specifications Operating 10g peak acceleration 7 5g DIN rail mounted 3 11 1 ms duration 3 times each direction each axis Non operating 20g peak acceleration 11 1 ms duration 3 times each direction each axis 3 Relays are derated an additional 2 5g on 20 pt controllers Terminal Screw Tor...

Page 24: ...itation On State Voltage Minimum 18V ac 14V dc Nominal 24V ac 24V dc Maximum 26 4V ac at 55 C 131 F 30V ac at 30 C 86 F 26 4V dc at 55 C 131 F 30V dc at 30 C 86 F On State Current Minimum 3 0 mA at 18V ac 2 5 mA at 14V dc Nominal 8 0 mA at 24V ac 8 0 mA at 24V dc Maximum 12 mA at 30V ac 12 mA at 30V dc Off State Voltage Minimum 0 0V ac 0 0V dc Maximum 3 0V ac 5 0V dc Off State Current Minimum 1 0 ...

Page 25: ... enabled the maximum update for each channel is equal to one ladder scan time plus the channel s Update Time plus Settling Time When only one analog input channel is enabled the maximum update for the channel is equal to the Update Time plus one ladder scan time for all except the first update after Going to Run GTR The first update time is increased by the Settling Time Settling Time mSec 1 Resol...

Page 26: ... break ratings for relay contacts cannot exceed 2A For dc voltage applications greater than 48V the make break ratings for relay contacts cannot exceed 1A 1 0A 28 VA 24V dc 1 2A 1 2 0A Description Specification Voltage Output Range 0 to 10V dc 1LSB Current Output Range 4 to 20 mA 1LSB Type of Data 16 bit signed integer Non linearity 0 02 Step Response 2 5 ms at 95 Load Range Voltage Output 1K Ω to...

Page 27: ...MicroLogix 1000 Programmable Controllers 27 Publication 1761 IN001C EN P March 2008 Notes efesotomasyon com Allen Bradley Rockwell plc servo drive ...

Page 28: ...28 MicroLogix 1000 Programmable Controllers Publication 1761 IN001C EN P March 2008 Notes efesotomasyon com Allen Bradley Rockwell plc servo drive ...

Page 29: ...amples informations concernant votre automate Installieren Sie die Steuerung mit Hilfe dieser Scha blone Weitere Informationen ber die Steuerung befinden sich auf der ersten Seite des in deutscher Sprache abgefaûten Abschnitts Usate questa maschera per installare il controllore Per ulteriori informazioni sul controllore fate riferi mento alla prima pagina della sezione nella vostra lingua Use esta...

Page 30: ...efesotomasyon com Allen Bradley Rockwell plc servo drive ...

Page 31: ...allation Assistance If you experience a problem with a hardware module within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operati...