1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Power Supply Instruction Manual
1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Bedienungsanleitung für Stromversorgung
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperatures of 60°C
(for ambient up to 45°C) and 75°C (for ambient up to 60°C). Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except for the
PE wire). Ferrules are allowed, but not required. Unused terminal spaces must be closed.
1606-XLEDNET3:
Solid wire / Stranded wire / AWG
0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length
7mm / 0.28inch
Tightening torque
0.8Nm / 7lb.inch
1606-XLSDNET4:
Input
terminals:
Solid wire / Stranded wire / AWG
0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length
7mm / 0.28inch
Output and signal terminals:
Solid wire / Stranded wire / AWG
0.3-4mm
2
/ 0.3-2.5mm
2
/ 26-12 AWG
Wire stripping length
6mm / 0.25inch
1606-XLSDNET8:
Solid wire / Stranded wire / AWG
0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length
7mm / 0.28inch
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für 60°C bei einer Umgebungstemperatur
bis zu 45°C und 75°C bei einer Umgebungstemperatur bis zu 60°C zugelassen sind. Beachten
Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine
einzelnen Drähte von Litzen abstehen. Bis zu zwei Leiter mit gleichem Querschnitt sind in einem
Anschlusspunkt zulässig (außer beim Schutzleiter). Aderendhülsen sind erlaubt, aber nicht
erforderlich. Nichtbenutzte Klemmen immer zudrehen.
1606-XLEDNET3:
Starrdraht / Litze / AWG
0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge
7mm
/
0,28inch
Empf. Anzugsdrehmoment
0,8Nm / 7lb.inch
1606-XLSDNET4:
Eingangsklemmen:
Starrdraht / Litze / AWG
0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge
7mm
/
0,28inch
Ausgangs- und Signalklemmen:
Starrdraht / Litze / AWG
0,3-4mm
2
/ 0,3-2,5mm
2
/ 26-12 AWG
Abisolierlänge
6mm
/
0,25inch
1606-XLSDNET8:
Starrdraht / Litze / AWG
0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge
7mm
/
0,28inch
Output- and Overload Characteristic
(see Fig. 5)
The units are overload, no-load, short-circuit proof. At overload, the output current flows
continuously. The unit does not switch-off or hiccup at overload.
Ausgangs- und Überlastverhalten
(siehe Bild 5)
Die Geräte sind leerlauf-, überlast- und kurzschlussfest. Bei Überlast fließt kontinuierlich Strom.
Die Geräte schalten nicht ab und haben auch keinen „Hiccup“ Modus.
DC-OK Relay Contact
except 1606-XLEDNET3 (see Fig. 6)
This feature monitors the output voltage, which is produced by the power supply, and is
independent of a return voltage from a unit which is connected in parallel.
Contact closes
when the output voltage reaches 20.5V
Contact opens
when the output voltage dips more than 10%. Short dips will be extended to a
length of 250ms. Dips shorter than 1ms will be ignored.
Contact ratings:
max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, Resistive load, min.: 1mA
DC-OK Relais Kontakt
außer 1606-XLEDNET3 (siehe Bild 6)
Diese Funktion überwacht die vom Gerät erzeugte Ausgangsspannung und lässt sich von einer
rückwärts eingespeisten Spannung nicht beeinflussen (z.B.: bei Parallelschaltung)
Kontakt schließt
sobald die Ausgangsspannung 21,5V erreicht
Kontakt öffnet
sobald der Ausgang um mehr als 10% einbricht. Kurze Einbrüche werden auf
250ms verlängert. Einbrüche kürzer 1ms werden ignoriert.
Belastbarkeit
: max.: 60Vdc 0,3A; 30Vdc 1A; 30Vac 0,5A; (R-Last); min.: 1mA
Dielectric Strength
(see Fig. 4)
The output voltage is floating and separated from the input according to SELV (IEC/EN 60950-1)
and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 60364-4-41) requirements. Type and factory
tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down).
Connect phase and neutral together as well as all output poles before the test is conducted.
A B
C
D
Type Test (60s)
2500Vac
3000Vac
500Vac
500Vac
Factory Test (5s)
2500Vac
2500Vac
500Vac
500Vac
Field Test (5s)
2000Vac
2000Vac
500Vac
500Vac
Isolationsfestigkeit
(siehe Bild 4)
Die Ausgangsspannung hat keinen galvanischen Bezug zur Erde oder Schutzleiter und ist zum
Eingang nach den SELV (IEC/EN 60950-1) und PELV (EN 60204-1, EN 50178, IEC 62103, IEC
60364-4-41) Standards getrennt. Typ- und Stückprüfungen werden beim Hersteller durchgeführt.
Wiederholungsprüfungen dürfen mittels geeigneten Prüfgenerators mit langsam (2s) ansteigenden
und abfallenden Spannungsrampen in der Anwendung erfolgen. Vor den Tests sind Phase und
Neutralleiter wie auch alle Ausgangspole miteinander zu verbinden.
A B C D
Typprüfung (60s)
2500Vac
3000Vac
500Vac
500Vac
Stückprüfung (5s)
2500Vac
2500Vac
500Vac
500Vac
Wiederholungsprüfung (5s)
2000Vac
2000Vac
500Vac
500Vac
Fig. 1 / Bild 1
1606-XLEDNET3: Functional Diagram / Funktionsschaltbild
Fig. 2 / Bild 2
1606-XLSDNET4: Functional Diagram / Funktionsschaltbild
Fig. 3 / Bild 3
1606-XLSDNET8: Functional Diagram / Funktionsschaltbild
+
+
-
-
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
NTC Inrush
Limiter
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
lamp
DC-ok
lamp
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
L
N
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
lamp
DC-ok
lamp
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
V
OUT
L
N
Fig. 4 / Bild 4
Insulation / Isolation
Fig. 5 / Bild 5
Overload Characteristic / Überlastverhalten
Fig. 6 / Bild 6
DC-OK Signal (except / außer 1606-XLEDNET3)
A
D
C
B
B
Input
DC-ok
Earth
Output
-
+
N
L
Output Voltage
0
0
2
6
8
10A
4
8
12
28V
16
20
24
4
Output Current
a) 1606-XLEDNET3
b) 1606-XLSDNET4
c) 1606-XLSDNET8
a b
c
250ms
21.5V
<1ms
open
24V
open
closed
closed
>1ms
Fig. 7 / Bild 7
Physical Dimensions / Abmessungen
1606-XLEDNET3
1606-XLSDNET4
1606-XLSDNET8
10000075774
(version 00)
PU-348.011.39-10A