Rock Solid Metered PDU Manual GS Geiger Group ∙ 181 Sand Creek Rd Ste I-1 ∙ Brentwood ∙ CA ∙ 94513 ∙ USA
8
5.5.
Checking the PDU Load
The total input load in amps is shown at the top of the screen under the Rock Solid logo. Clicking on the
PDU link off the main menu also shows the PDU input load and the current threshold values.
5.6.
Checking and Changing System Parameters
Clicking on the System link off the main menu displays the system parameters. The model name, firmware
version, MAC address, SNMP System Name, SNMP System Contact and SNMP Location are shown. The
SNMP values can be changed by doing the following.
1.
From the main menu, click on the SNMP link.
2.
Enter System Name.
3.
Enter System Contact.
4.
Enter Location.
5.
Click Apply. A confirmation dialog box will pop up, click OK to save the new values.
5.7.
Checking and Changing the Threshold Values
The PDU has 2 threshold values, the Warning threshold and the Overload threshold values. If the input
current crosses the Warning threshold, then the PDU will beep with the frequency, 1 beep per second. If the
input current crosses the Overload threshold, then the PDU will beep with the frequency, 3 beeps per
second.
The audible alert will keep beeping until the current goes back 0.5 amps below the threshold value. The
Warning alert can be manually disabled, see instructions on the Function Button. The Overload alert cannot
be manually disabled.
To change the threshold values, do the following:
1.
From the main menu, click on the Threshold link
2.
Enter the new Warning and Overload values
3.
Click Apply. A confirmation dialog box will pop up, click OK to save the new values.