![Roca BCH-10 Technical Information Download Page 11](http://html1.mh-extra.com/html/roca/bch-10/bch-10_technical-information_1472021011.webp)
11
Installation instructions
General
The BCH heat pumps are delivered as factory charged and
tested packaged units. Designed to be installed with ducts,
on terraces, rooftops, in lofts or basements.
Protection of the environment
Packing
Packing is made of recyclable material. The disposal of same
should be carried out in accordance with the regulations on
selective residue disposal established by the local authori-
ties.
Disposal of the unit
When dismantling after a long service life, its components
should be ecologically salvaged. The cooling circuit is full of
HCFC-22 refrigerant which should be salvaged and, finally,
returned to the gas manufacturer for recycling.
Oil will remain in the airtight compressor so, it will be returned
along with the sealed circuit.
The air conditioning unit will be deposited wherever estab-
lished by the local authorities for its selective disposal.
Warning signs
The following signs indicate the presence of potentially
dangerous conditions for the users or service personnel.
Whenever found on the unit itself, keep in mind the warning
indicated by each one.
Transport
The units should always be transported in a vertical position
to prevent oil from leaking out of the compressor. If for some
reason the unit must be temporarily moved from this position,
the time that it rests in a different position should be kept to
a minimum.
Location
The unit should be placed in a location that leaves a perma-
nent access for maintenance service, either through the side
panels, or top cover.
They can be installed in any outdoor location. If installed
indoors in basements, lofts, etc., the ducts for outdoor air
intake and exhaust should be connected.
When the unit is installed indoors, consideration should be
given to the great quantity of water condensed by the outdoor
coil during winter operation, that must be drained through the
drain pipe.
Occasionally, when the operating cycle is reversed in winter
to remove the frost that forms on the coil, the air could carry
water droplets. This should therefore be kept in mind when
selecting the place of installation and also the possibility of
Attention: It is compulsory to read the
instructions prior to any handling.
This sing indicates an electrical risk or
danger.
Attention: Not to touch the hot surfaces.
Attention: The unit has remote control
system and can start automatically. Two
minutes prior to having access to the
interior, the power supply should be
disconnected so as to avoid any contact
with the fan turbine in operation.
Attention: Fan in operation.