Robur Supercromo Installation, Use And Maintenance Manual Download Page 23

Maintenance 

Installation, use and maintenance manual – Supercromo 

23

7

 

Case 2: the status of the programmer clock output is 

"OFF" (red LED off)

1.  Press the MANUAL button to move the indicator from 

"AUTO" to "ON", the programmable timer output will 

change to the state "ON" and the red LED will light up; 

this way, the set programs will be skipped.

2.  To reactivate the running of the set programs, press the 

MANUAL button again, the indicator will move from 

"ON" to "AUTO" but the output of the programmable 

timer will continue to stay "ON" (red LED on). The pro-

grammable timer will resume its automatic operation 

when the next program will switch to the status "OFF" 

(i.e. until the status of the request is changed).

7  

 MAINTENANCE

 

7.1 

 

 WARNINGS

Correct maintenance prevents problems, assures 

efficiency and keeps running costs low.

Any operation on internal components may exclu-

sively be performed by the TAC.

Before performing any operation, switch off the 

appliance by means of the control device and wait 

for the end of the shutdown cycle, then disconnect 

power and gas supply, by acting on the electrical 

disconnector and gas valve.

The efficiency checks and every other "check and 

maintenance operation" must be performed with 

a frequency according to current regulations or, 

if more restrictive, according to the provisions set 

forth by the manufacturer, installer or TAC.

Responsibility for efficiency checks, to be carried 

out for the aims of restricting energy consumption, 

lies with the system manager.

7.2 

   CLEANING AND MAINTENANCE

The only operation required by this kind of gas-fired con-

vector is the cleaning of the outer casing (which must al-

ways be carried out with the appliance cold and without 

the use of solvents) and the periodic removal of any dust 

that may accumulate on the heat exchanger and the fan.

It is recommended to have a periodic (annual) check and 

cleaning of the gas-fired convector by contacting a TAC.

With regard to periodic maintenance of the gas-fired con-

vector, follow the regulations in force.

7.3 

 

 SAFETY  DEVICES

Electricity outage

The gas-fired convector is switched off by closing 

the gas valve. When the power supply is restored, 

the gas-fired convector will automatically restart.

Gas failure or other faults that causes the flame 

to extinguish

The gas-fired convector will automatically attempt 

to restart for a period of 10 seconds, after which, if 

the attempt fails, the control unit will lock out the 

gas-fired convector and stop the blower (red signal 

light lit on the control panel).

Overheating

If during operation the upper or lower grille is 

partially obstructed or the fan stops, causing the 

gas-fired convector to overheat, the limit thermo-

stat trips, cutting off the power supply to the gas 

valve, interrupting the flow of gas to the burner. To 

restore operation, wait about ten minutes for the 

temperature to drop, disconnect the gas-fired con-

vector from the power supply, remove the casing 

and reset the limit thermostat by pressing the reset 

button located on the limit thermostat itself (detail 

A in Figure 7.1 

p.  23). If the problem is repeated 

within a short period of time, TAC must be called in 

to check the causes of overheating.

Figure 7.1  

 Limit  thermostat

A  Limit thermostat

A

7.4 

   ANY MALFUNCTIONS OF OPERATION

Before taking any particular measures, always check that:

Summary of Contents for Supercromo

Page 1: ...Installation use and maintenance manual Supercromo Fired by natural gas LPG Independent gas fired convectors with direct exchange to heat small and medium sized rooms...

Page 2: ...ered trademarks contained within this publication are not affected With the aim of continuously improving the quality of its products Robur S p A reserves the right to modify the data and contents of...

Page 3: ...p 9 2 3 Appliance positioning p 10 2 4 Minimum clearance distances p 10 3 Heating engineer p 10 3 1 Warnings p 10 3 2 Supplied material p 10 3 3 Fuel gas supply p 10 3 4 Combustion products exhaust p...

Page 4: ...al local regulations in force and the manu facturer s instructions provisions Misuse The appliance must only be used for the purpos es for which it has been designed Any other use is deemed hazardous...

Page 5: ...s paints etc near the appliance Comply with current regulations Aggressive substances in the air The air of the installation site must be free from ag gressive substances Switching the appliance off D...

Page 6: ...on products exhaust Fire safety and prevention Any other applicable law standard and regulation III 3 EXCLUSIONS OF LIABILITY AND WARRANTY Any contractual or extra contractual liability of the manufac...

Page 7: ...operation of the gas fired convector very simple in itself is made completely automatic by the thermostatic regulation and the programmable timer standard in the 3002 model optional in the 3001 model...

Page 8: ...and 3 Serial con nection of the coils terminals 2 and 4 F A Noise filter L Line M1 Limit thermostat M2 Fan thermostat M4 Control unit M9 2 A fuse N Neutral P1 Reset button RP7 Ignition electrode RP8 D...

Page 9: ...C33 C63 residual head Pa 25 maximum equivalent length of coaxial exhaust duct m 1 sound power Lw max dB A 47 5 sound pressure Lp at 5 metres max dB A 28 5 Dimensions width mm 478 height mm 577 depth m...

Page 10: ...ommended distance from the gas fired convector to the floor is 13 cm Figure 1 1 p 8 and possibly not more than 35 cm as higher heights would result in uneven heat distribution in the heated room Keep...

Page 11: ...ce pipe union Perform connection in compliance with applicable regulations 3 3 3 Gas pipes sizing The gas pipes must not cause excessive pressure drops and consequently insufficient gas pressure for t...

Page 12: ...ar Figure 1 1 p 8 3 4 2 Installation types The flue gas exhaust combustion air intake of the Supercromo gas fired convectors can be realised in one of the following ways With coaxial pipes with outlet...

Page 13: ...installed with separate pipes suitable pipes and components available as optional must be used At the design stage it must be verified that the sum of the pressure drop of all components used does no...

Page 14: ...r intake and flue gas exhaust pipes Do not damage or discard the cardboard jig with the drilling template required for installing the gas fired convector 3 Fix the jig to the wall where the gas fired...

Page 15: ...e complete with heating body by loosening the fixing screws see Figure 3 7 p 15 and disconnect the casing earth cable 10 Fit the end of the flue gas exhaust pipe 35 mm onto the gas fired convector out...

Page 16: ...not to work on live components Earthing The appliance must be connected to an effective earthing system installed in compliance with reg ulations in force It is forbidden to use gas pipes as earthing...

Page 17: ...y Appliance defects or faults caused during transport or installation Gas smell Non compliant mains gas pressure Non compliant flue gas exhaust All situations that may involve operation abnormali ties...

Page 18: ...e regula tor B by fully tightening its screw and adjusting the second stage regulator if necessary 6 When the adjustment is complete switch off the appliance After the adjustment stop and start the ap...

Page 19: ...Reassemble the plug B 8 Turn on the gas fired convector and check the gas tightness of plug B 9 Check the gas pressure at the burner as described in Paragraph 5 2 1 p 17 10 Remove the LPG adhesive lab...

Page 20: ...iance and the blower stops lighting up red signal light C The reset must be carried out manually using reset button A 8 Once the appliance is switched on turn knob B on the thermostat clockwise to inc...

Page 21: ...n of the fan ther mostat by running the cables under the bracket 7 Use cable 93 black of the cable kit to connect the pro grammable timer terminals 2 and 4 to each other 8 Remove the room thermostat d...

Page 22: ...wanted switching on and or switching off Pressing the TIMER button the on off programs set will be displayed Figure 6 4 15 combination of days in a week 1 From Monday to Sunday 2 Monday 3 Tuesday 4 We...

Page 23: ...of gas fired con vector is the cleaning of the outer casing which must al ways be carried out with the appliance cold and without the use of solvents and the periodic removal of any dust that may accu...

Page 24: ...odes is broken or badly posi tioned replace it or reposition it For a correct ignition the distance between the two ignition electrodes must be about 3 5 mm D The detection electrode is broken or badl...

Page 25: ...ons possible room temperature control with presence detec on room temperature control with open window detec on with distance control op on with adap ve start control with working me limita on with e...

Page 26: ...h presence detec on room temperature control with open window detec on with distance control op on with adap ve start control with working me limita on with electronic room temperature control plus we...

Page 27: ......

Page 28: ...on of safe environmentally friendly energy efficiency products through the commitment and caring of its employees and partners Robur S p A advanced technologies for air conditioning via Parigi 4 6 240...

Reviews: