GAHP-W – Installation, start-up, use and maintenance manual
8
Edition:
2014-08
2.1 GAHP-W – TECHNICAL SPECIFICATIONS
GAHP-W GAHP-W
LB
PERFORMANCE RATINGS
EVAPORATOR INLET TEMPERATURE (COLD SIDE)
°F
50
32
CONDENSER OUTLET TEMPERATURE (HOT SIDE)
°F
122
122
HEATING CAPACITY
(1)
kBtu/h 132.4
119.4
EFFICIENCY (HEATING)
%
139
125
CHILLING CAPACITY
(1)
kBtu/h 54.6
46.1
EFFICIENCY (CHILLING)
%
57
48
HOT WATER FLOW RATE
GPM 14.5
13.2
∆
T HOT SIDE
°F
18
18
HOT SIDE PRESSURE DROP (CONDENSER)
Ft (WC)
PSIg
12.7
5.51
10.5
4.50
CHILLED WATER FLOW RATE
GPM
12.3
11.0
∆
T COLD SIDE
°F
9
9
COLD SIDE PRESSURE DROP (EVAPORATOR)
kPa
PSIg
12.7
5.51
15.4
6.67
OPERATIONAL LIMITS
COLD SIDE WATER FLOW RATE (EVAPORATOR) – MIN/MAX
GPM 10.1/20.7 8.8/17.6
EVAPORATOR MAXIMUM INLET TEMPERATURE
°F
113.0
113.0
EVAPORATOR MINIMUM OUTLET TEMPERATURE
°F
37.4
23.0
HOT SIDE WATER FLOW RATE (CONDENSER) – MIN/MAX
GPM
6.2/22.0
HOT WATER MINIMUM RETURN TEMPERATURE IN CONTINUOUS
OPERATION
(6)
°F 68
CONDENSER MAXIMUM INLET TEMPERATURE
°F +113.0
CONDENSER MINIMUM INLET TEMPERATURE
°F +35.6
CONDENSER MAXIMUM OUTLET TEMPERATURE
°F
149
140
AMBIENT TEMPERATURE - MIN/MAX °F
10.4/113.0
BURNER SPECIFICATIONS
NOMINAL HEAT CAPACITY (14.4 PSI – 68 °F)
kBtu/hr
95.5
ELECTRICAL RATINGS
REQUIRED VOLTAGE, 60HZ, SINGLE PHASE
(2)
V 208-230
MINIMUM CIRCUIT AMPACITY (MCA) Unit only
A
15
MAXIMUM OVER CURRENT PROTECTION (MOCP)
A
15
TOTAL ELECTRICAL OPERATING CONSUMPTION (NOMINAL)
(3)
kW 0.4
PHYSICAL DATA
OPERATING WEIGHT
Pounds
630.5
WATER VOLUME PER WATER CIRCUIT
(4)
Gallons 0.79
DIMENSIONS WIDTH
DEPTH
HEIGHT
Inches
33-
1
/
4
25-
3
/
4
50-
3
/
4
INLET/OUTLET WATER PIPE DIAMETERS
FPT
1” 1/4
GAS PIPE DIAMETER
FPT
1
/
2
DIAMETER EXHAUST FLUE PIPE
(5)
Inches 3-
1
/
8
Table 2
-
GAHP-W performance ratings and operational limits.
(1) ALL ILLUSTRATIONS AND SPECIFICATIONS CONTAINED HEREIN ARE BASED ON THE LATEST INFORMATION AVAILABLE AT
THE TIME OF PUBLICATION APPROVAL. ROBUR RESERVES THE RIGHT TO MAKE CHANGES AT ANY TIME WITHOUT NOTICE, IN
MATERIALS, SPECIFICATIONS, AND MODELS OR TO DISCONTINUE MODELS.
(2) UNITS ARE FACTORY-WIRED FOR 230 VOLT OPERATION.
(3) MAY VARY BY ±10% AS A FUNCTION OF BOTH POWER SUPPLY AND ELECTRICAL MOTOR INPUT TOLERANCE.
(4) THE UNIT HAS 2 WATER CIRCUITS. THE VALUE IS REFERRED TO A SOLUTION OF QUALITY TAP WATER AND 10% BY VOLUME
OF INHIBITED PERMANENT ANTIFREEZE. HIGHER ANTIFREEZE CONCENTRATIONS MAY BE REQUIRED IN CERTAIN
APPLICATIONS. MONO-ETHYLENE GLYCOL MAY CAUSE CORROSION IN GALVANIZED METAL PIPES.
(5) FOR EXHAUST DUCT DIMENSIONS SEE , PAGE 62.
(6) IN TRANSIENT OPERATION, LOWER TEMPERATURES ARE ALLOWED.