Heating engineer
Installation, use and maintenance manual – Next-G
31
3
3.3.3.3
C13 type installation with separate ducts
Figure 3.3
C13 type installation with Ø 80 separate ducts
Table 3.4
C13 type maximum allowed length with separate
ducts
Indicative maximum lengths (m)
Next-G
Air pipe
Flue gas exhaust pipe
Ø 80
Ø 100
Ø 110
Ø 80
Ø 100
Ø 110
G 20 EC
30
30
30
30
30
30
G 30, G 30 EC
30
30
30
30
30
30
G 35 EC
22
30
30
22
30
30
G 45, G 45 EC
19
30
30
19
30
30
G 60, G 60 EC
15
30
30
15
30
30
G 75 EC
10
30
30
10
30
30
G 90, G 90 EC
11
30
30
11
30
30
3.3.3.4
C13 type installation with wall coaxial terminal
Figure 3.4
C13 type installation with wall coaxial terminal and
Ø 80 ducts
Table 3.5
C13 type maximum allowed length with 80/125 wall
coaxial terminal and Ø 80 ducts
Indicative maximum lengths (m)
Next-G
Air pipe
Flue gas exhaust pipe
G 20 EC
30
30
G 30, G 30 EC
29
29
G 35 EC
20
20
G 45, G 45 EC
16
16
G 60, G 60 EC
12
12
G 75 EC
8
8
G 90, G 90 EC
8
8
Table 3.6
C13 type maximum allowed length with 130/180 wall
coaxial terminal
Indicative maximum lengths (m)
Next-G
Air pipe
Flue gas exhaust pipe
Ø 80
Ø 130
Ø 80
Ø 130
G 20 EC
30
30
30
30
G 30, G 30 EC
30
30
30
30
G 35 EC
21
30
21
30
G 45, G 45 EC
18
30
18
30
G 60, G 60 EC
14
30
14
30
G 75 EC
9
30
9
30
G 90, G 90 EC
9
30
9
30
3.3.3.5
C33 type installation with roof coaxial terminal
Figure 3.5
C33 type installation with roof coaxial terminal
Table 3.7
C33 type maximum allowed length with 80/125 roof
coaxial terminal and Ø 80 ducts
Indicative maximum lengths (m)
Next-G
Air pipe
Flue gas exhaust pipe
G 20 EC
30
30
G 30, G 30 EC
25
25
G 35 EC
15
15
G 45, G 45 EC
11
11
G 60, G 60 EC
7
7
G 75 EC
2
2
G 90, G 90 EC
2
2
Table 3.8
C33 type maximum allowed length with 100/150 roof
coaxial terminal
Indicative maximum lengths (m)
Next-G
Air pipe
Flue gas exhaust pipe
Ø 80
Ø 100
Ø 80
Ø 100
G 20 EC
30
30
30
30
G 30, G 30 EC
27
30
27
30
G 35 EC
18
30
18
30
G 45, G 45 EC
14
30
14
30
G 60, G 60 EC
10
30
10
30
G 75 EC
5
20
5
20
G 90, G 90 EC
5
19
5
19