Appendix A: technical data
Installation manual – Expansion kit
23
7
APPENDIX A: TECHNICAL DATA
RVS21�826, QAA75�611, QAA55�110
Refer to Appendix A of the system controller Installation manual.
AVS55�196
Table
AVS55.196 technical data
Power supply
Supply voltage
AC 230 V (+10%/-15%)
Frequency
50 / 60 Hz
Consumption
max. 2.5 VA
Power supply protection
Thermal-magnetic circuit breaker: max. 13 A (EN60898-1)
or
fuse: max. 10 AT
Cabling
230 VAC supply and outputs; bars or braided
cables (with/without terminals)
1cable: 0.5 - 2.5 mm²
2cables: 0.5 - 1.5 mm²
Inputs
Digital inputs H31, H32, H33
Open contact voltage
Closed contact current
Safety Extra Low Voltage (SELV) for voltage free contacts
DC 12 V
DC 3 mA
Analogue inputs H31, H32, H33
• Functional range
• Internal resistance
Safety Extra Low Voltage (SELV)
DC 0 - 10 V
> 100 kΩ
Pulse count inputs H31, H32, H33
• Open contact voltage
• Closed contact current
• Pulse duration
Safety Extra Low Voltage (SELV) for voltage free contacts
DC 12V
DC 3 mA
min. 20 ms
Frequency measurement inputs H31, H32, H33
• Functional range
• Low state voltage
• High state voltage
• Internal resistance
• Frequency
Safety Extra Low Voltage (SELV)
DC 0 - 12 V
< 1.7 V
2.7 - 12 V
> 100 kΩ
max. 500 Hz
Sensor inputs BX31 - BX34
NTC 1k (QAC34, external sensor),
NTC 10k (QAZ36, QAD36),
Pt1000 (optional for solar collector and exhaust gas sensor)
5053…9671 Ω (room setpoint modification function)
Sensor cables (copper)
• Cross section
• Max. length
-
0.25
0.5
0.75
1.0
1.5 (mm²)
20
40 60 80 120
(m)
Outputs
Relay outputs QX31…QX33, QX35
• Current range
• Switching ON current
• Total current
-
AC 0.02 - 2 (2) A
max. 15 A for ≤1 s
max. AC 10 A (total, all 230 VAC outputs)
Triac output ZX34
• Current range
• Switching ON current
• Total current
-
AC 0.02 - 2 (2) A (On/Off operation); AC 0.02 - 1.2 (1.2) A (speed control)
max. 4 A for ≤1 s
max. AC 10 A (total, all 230 VAC outputs)
Power G+
• Output voltage
• Current
Safety Extra Low Voltage (SELV), outputs with short-circuit protection
11.3 - 13.2 V
max. 88 mA (including RVS21 and AVS55)
Power GX1 (configurable)
• Output voltage 5 V
• Output voltage 12 V
• Current
Safety Extra Low Voltage (SELV), outputs with short-circuit protection
4.75 - 5.25 V
11.3 - 13.2 V
max. 20 mA (including RVS21 and AVS55)
Interfaces
BSB
Base unit/peripheral cable length
Total cable length
Cross section
Two-wire connection (not invertible)
max. 200 m
max. 400 m (max. cable capacity: 60 nF)
min. 0.5 mm²
Connection cable X100 to expansion module
AVS55.19x
• Cable length
-
ribbon cable (18 pole)
max. 1000 mm
Protection rating and
safety class
Enclosure protection rating per EN60529
IP 00 (without enclosure)
Safety class per EN60730
safety class II for LV parts, if correctly installed
Degree of contamination per EN60730
degree of contamination normal
Standards, safety, EMC, etc.
CE conformity (EU)
CE1T2355xx06
Climatic conditions
Storage, per EN60721-3-1
Transport, per EN60721-3-2
Operation, per EN60721-3-3
class 1K3, -20 - 65 °C
class 2K3, -25 - 70 °C
class 3K5, -20 - 50 °C (non condensing)
Weight
Packaging excluded
112 g