Direct Digital Controller
Direct Digital Controller fw 4.013 – Ed. 01/2013
153
managed by an RB200 device, is unusable (malfunction or off-line). The error halts the system (the generators
are switched off), and clears when the cause generating it has been removed.
The error occurs if the off-line or malfunction error on one or more corresponding probes persists for 1 minute.
The error clears when the corresponding off-line or malfunction errors are no longer present for at least 1
minute.
E 1031
C(H) IN T Prb Offlin (2-line Cooling or Cooling/Heating Plant Return Probe Off-line)
This error is generated if communication between the DDC and the RB200 managing the probe in question is
interrupted.
The error may also be generated when updating the RB200 and/or reconfiguring the module managing the
probe, not followed by a new "machine configuration" on the DDC.
The error halts the system (the generators are switched off) if the DDC uses this probe to regulate the plant; in
this case it is present together with error E1029.
The error clears off in the event of a communication reset or completion of the configuration, depending on the
cause which generated it.
E 1032
C(H) OUT T Prb Offlin (2-line Cooling or Cooling/Heating Plant Delivery Probe Off-line)
See description
E 1031
E 1033
H IN T Probe Offline (Heating Plant Return Probe Off-line)
See description E 1031
E 1034
H OUT T Probe Offline (Heating Plant Delivery Probe Off-line)
See description E 1031
E 1035
Sep IN T Probe Offln (Separable Plant Part Return Probe Offl-ine)
This error is generated if communication between the DDC and the RB200 managing the probe in question is
interrupted.
The error may also be generated when updating the RB200 and/or reconfiguring the module managing the
probe, not followed by a new "machine configuration" on the DDC.
The error halts the system (the generators are switched off) if the DDC uses this probe to regulate the plant; in
this case it is present together with error E1030.
The error clears off in the event of a communication reset
or
completion of the configuration, depending on the
cause which generated it.
E 1036
Sep OUT T Probe Offln (Separable Plant Part Delivery Probe Offl-ine)
See description E 1035.
E 1037
GAHP IN T Prb Offlin (Heat Pump Return Probe Off-line)
See description E 1031.
E 1038
C(H) IN T Prb Conflt (2-line Cooling or Cooling/Heating Plant Return Probe Configuration Conflict)
The error is generated in the event that another device with the same ID is configured on the communication
network.
This error does not halt the system.
E 1039
C(H) OUT T Prb Conflt (2-line Cooling or Cooling/Heating Plant Delivery Probe Configuration Conflict)
See description E 1038.
E 1040
H IN T Probe Conflt (Heating Plant Return Probe Configuration Conflict)
See description E 1038.
E 1041
H OUT T Probe Conflt (Heating Plant Delivery Probe Configuration Conflict)
See description E 1038.
E 1042
Sep IN T Prb Conflt (Separable Plant Part Return Probe Configuration Conflict)
See description E 1038.
E 1043
Sep OUT T Prb Conflt (Separable Plant Part Delivery Probe Configuration Conflict)
See description E
1038
E 1044
GAHP IN T Prb Conflt (Heat Pump Return Probe Configuration Conflict)
See description E 1038.
E 1045
C(H) IN T Prb Malf (2-line Cooling or Cooling/Heating Plant Return Probe Malfunction)
This error is
generated in the event of an error or absence on the probe in question. The error halts the system (the
generators are switched off) if the DDC uses this probe to regulate the plant; in this case it is present together