Appendices
Installation, use and maintenance manual – GAHP A
37
APPENDICES
PRODUCT FICHE
Figure
Model(s):
GAHP A HT
Air-to-water heat pump:
yes
Water-to-water heat pump:
no
Brine-to-water heat pump:
no
Low-temperature heat pump:
no
Equipped with a supplementary heater:
no
Heat pump combination heater:
no
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Rated heat output (*)
Prated
29,6
kW
Seasonal space heating
energy efficiency
η
s
111
%
Tj = -7 °C
Pdh
26,1
kW
Tj = -7 °C
PERd
96
%
Tj = +2 °C
Pdh
16,0
kW
Tj = +2 °C
PERd
120
%
Tj = +7 °C
Pdh
10,4
kW
Tj = +7 °C
PERd
117
%
Tj = +12 °C
Pdh
4,4
kW
Tj = +12 °C
PERd
111
%
T
j
= bivalent temperature
Pdh
-
kW
Tj = bivalent temperature
PERd
-
%
Annual energy consumption
Q
HE
198
GJ
Rated heat output (*)
Prated
29,4
kW
Seasonal space heating
energy efficiency
η
s
107
%
Tj = -7 °C
Pdh
17,9
kW
Tj = -7 °C
PERd
109
%
Tj = +2 °C
Pdh
10,9
kW
Tj = +2 °C
PERd
117
%
Tj = +7 °C
Pdh
7,1
kW
Tj = +7 °C
PERd
112
%
Tj = +12 °C
Pdh
3,2
kW
Tj = +12 °C
PERd
111
%
Tj = bivalent temperature
Pdh
-
kW
Tj = bivalent temperature
PERd
-
%
T
j
= operation limit
temperature
Pdh
29,4
kW
Tj = operation limit
temperature
PERd
87
%
For air-to-water heat pumps:
T
j
= –15 °C (if TOL < –20 °C)
Pdh
24,1
kW
For air-to-water heat pumps:
Tj = –15 °C (if TOL < –20 °C)
PERd
90
%
Annual energy consumption
Q
HE
244
GJ
Rated heat output (*)
Prated
36,4
kW
Seasonal space heating
energy efficiency
η
s
116
%
Tj = +2 °C
Pdh
36,4
kW
Tj = +2 °C
PERd
119
%
Tj = +7 °C
Pdh
23,3
kW
Tj = +7 °C
PERd
122
%
Tj = +12 °C
Pdh
10,6
kW
Tj = +12 °C
PERd
116
%
Tj = bivalent temperature
Pdh
-
kW
Tj = bivalent temperature
PERd
-
%
Annual energy consumption
Q
HE
151
GJ
Table 8
COMMISSION DELEGATED REGULATION (EU) No 811/2013
Parameters shall be declared for average, colder and warmer climate conditions.
Technical parameters for heat pump space heaters and heat pump combination heaters
Parameters shall be declared for medium-temperature application.
Declared capacity for heating for part load at indoor
temperature 20 °C and outdoor temperature Tj
Declared coefficient of performance or primary energy
ratio for part load at indoor temperature 20 °C and
outdoor temperature Tj
AVERAGE CLIMATE CONDITIONS
Declared capacity for heating for part load at indoor
temperature 20 °C and outdoor temperature Tj
Declared coefficient of performance or primary energy
ratio for part load at indoor temperature 20 °C and
outdoor temperature Tj
Declared capacity for heating for part load at indoor
temperature 20 °C and outdoor temperature Tj
Declared coefficient of performance or primary energy
ratio for part load at indoor temperature 20 °C and
outdoor temperature Tj
COLDER CLIMATE CONDITIONS
WARMER CLIMATE CONDITIONS