background image

12.1

Check the Gas Pressure and F.S.D. Operation

Remove the pressure test point sealing screw and connect a pressure gauge to the test point. 

(a) Light the heater. Please refer to the Users Instructions. Turn the control knob to the full on position marked HIGH.

(b) Check that the burner pressure is as specified on page 3. Turn off the gas supply to the heater. Wait 3 minutes then

restore the gas supply. The pressure should read ZERO to confirm the FSD has shut off the gas. You may hear the FSD 

close, but you must confirm gas has stopped flowing. Remove the pressure gauge and replace the pressure test screw. 

Re-light the heater and test for gas soundness around the sealing screw using a suitable leak detection fluid.

(c) Check ignition performance.

WARNING: If you want to re-light a hot heater wait three minutes before doing so.

12.3

Instruct User (Refer to the Users Instructions)

Make sure that the user understands the following:-

(a) How to light and operate the heater.

(b) Demonstrate the removal and replacement of the glass door and the removal and replacement of the ceramics. Advise 

on the need to clean these items regularly.

(c) Advise that for safe and efficient operation, the heater should be serviced annually by a CORGI registered service 

agent.

(d) When the heater is first lit a slight smell may be noticed but this will quickly clear away with use.

Hand over these instructions to the user.

12.0 COMMISSIONING

11.0 GAS CONNECTION

11.1 Rear Entry Gas Supply Connection

IMPORTANT NOTE:

If rear entry gas supply connection is required, then it MUST be installed prior to the installation of 

the heater into the wall. If any pipe is run in or through the cavity, a factory sleeved pipe must be 

used and sealed where the pipe enters the fire and/or cavity.

(a) Position the gas supply pipe at the left hand side of the opening and fit the appliance inlet elbow which has a nut and 

olive suitable for 8mm pipe( see fig 9.). After the heater has been installed into the wall connect the appliance inlet 

elbow to the gas inlet pipe.

11.2 Front Entry Gas Supply Connection

IMPORTANT NOTE:

If front entry gas supply connection is required, then it MUST be installed after the installation of 

the heater into the wall.

(a) Loosen the nut on the appliance inlet elbow which is located at the lower left hand side of the appliance and turn the 

elbow to face either left or right as required.

(b) Connect the gas supply to the appliance inlet elbow which has a nut and olive suitable for 8mm pipe..

11.3Test for Gas Soundness. (Refer to BS 6891)

The gas installation, including the meter, should be inspected and tested for soundness and purged.

Fig 9.

14

Summary of Contents for BELVEDERE RS

Page 1: ...LEAVE THESE INSTRUCTIONS WITH THE USER The Data Badge and Serial Number are located on the left hand side of the base panel 1 Cat I G20 at 20mbar 2H For use in GB and IE RIVIERA RS BELVEDERE RS G C No...

Page 2: ...dust back into the air If a vacuum cleaner is recommended for use by your organisation you must use a HEPAfiltered vacuum to remove any dust and soot accumulated in and around the fire before and afte...

Page 3: ...17 15 0 SPARES AND SERVICE 19 16 0 SHORT LIST OF PARTS 19 TABLE OF FIGURES No DESCRIPTION PAGE 1 LINE DIAGRAM BELVEDERE ILLUSTRATED 2 2 TYPICAL INSTALLATION 6 3 FLUE TERMINAL LOCATION 7 4 CABLE FIXIN...

Page 4: ...d 994371 Gas Safety Installation and Use Regulations It is the law that all gas appliances are installed by competent persons in accordance with technical requirements The following items relate to th...

Page 5: ...to impact of any kind as breakage may occur 4 0 SAFETY 5 0 UNPACKING The heater is packed in a carton together with the following items 1 Flue pack 2 Gasket pack comprising flue and air duct gaskets...

Page 6: ...material of the surround must have a 150 C application i e marked with the suffix 150 If it is not feasible to cut an opening in the wall then a rebated surround with a 152 mm rebate should be used t...

Page 7: ...pipes 300mm F From internal or external corners 600mm G Above ground roof or balcony level 300mm H From a surface facing a terminal 600mm I From a terminal facing a terminal 600mm J From an opening i...

Page 8: ...f the outer section of the wall ensuring that its top is level and that the centre line of the flue is 427mm above the hearth level 7 3 Cut the hole for the flue making sure that it is straight and le...

Page 9: ...s of the ducts are marked TOP to indicate the way in which the ducts are to be fitted Note DO NOT remove the two middle slotted screws 8 7 Adjust the flue length First measure the wall thickness and a...

Page 10: ...cut the hole 135 mm diameter making allowances for the shrinkage of the timber frame d Measure the thickness of the combustible part of the wall and cut the flue liner to this length cutting off the e...

Page 11: ...tion 11 2 Front Entry Gas Connection iii An of isolation elbow is fitted at the inlet to the heater e Prise the tabs up on each side of the firebox using a screw driver Fit the cable tensioning bolts...

Page 12: ...e Fig 4 h Using a spanner unscrew each tensioning bolt by approximately 20 mm to tension the cable Prevent the cable adaptors from rotating while unscrewing the tensioning bolts i Coil excess cable an...

Page 13: ...e coal base and resting on the ledge of the rear coal Replacement is the reversal of removal Position the top edge centrally against the fire and slide upwards When meeting resistance of clip swing bo...

Page 14: ...by a CORGI registered service agent d When the heater is first lit a slight smell may be noticed but this will quickly clear away with use Hand over these instructions to the user 12 0 COMMISSIONING 1...

Page 15: ...ter is required see Fig 10 If there are no existingopenings or beams withineither triangle proceed withforming the opening However if openings or beams occurwithin either triangle either 1 Use the gui...

Page 16: ...Fig 12 13 5 Remove the masonry below the lintel and clear all the debris from the cavity Construct the opening to the size specified in Section 7 0 Non Combustible Wall Installation see Fig 4 A Rockw...

Page 17: ...heater Place to one side Refit after work is complete 14 2 Removing The Main Burner Remove the glass door and coals if burner is to be removed Refer to User instructions Remove the fender mask as sho...

Page 18: ...ple connection at the control Remove the two pilot mounting screws as shown below and remove the pilot taking care not to damage the gasket It is recommended to have a spare gasket available Refit in...

Page 19: ...n of the heater 16 0 SHORT LIST OF PARTS All these spares plus a comprehensive list are available by contacting the address below 14 10 Pressure Relief Panels If dealing with a complaint resulting fro...

Reviews: