19

4. 

As 3, but no spark visible 

Spark availability at electrode during spark period. 

during ignition period. 

Remove the spark lead from the electrode, hold with 
insulated pliers 3mm from earthed metal. If a spark is 
present examine the spark electrode for damage to 
insulation and check the spark gap. If no spark is present, 
check the continuity of the overheat switch and 
connections. If satisfactory the control board is faulty. 

5. 

Heater lights but goes to lock out 

Detection electrode and lead for short to earth. Gas supply 

condition. 

for continuity. 
Air supply blockage. 
Freedom of combustion fan rotor. 
Possible control board fault. 
Polarity of electrical supply. 

SHORT PARTS LIST

Key

No.

G.C.

No.

Part

No.

off

RW No.

Key

No.

G.C.

No.

Part

No.

off

RW No.

Convection Fan Assembly, ITT
13LL RMM/Wx 1596
Combustion Fan: Torin DSA 300
101/2286
Gasket: Combustion Fan
Air Intake Duct
Gasket: Burner Mounting Plate
Injector: (Natural Gas) RW N.9
Electrode Assembly including
Key No. 40
Gasket: Electrode
Solenoid Valve
Gasket: Injector Holder
Pressure Test Nipple Screw
Printed Circuit Board
Electrode

389 283

389 282

203 796
203 797
393 344
203 798
393 570

203 799

203 750
400 001
991 470
204 080

17

26

28
29
32
35
39

40
42A
49
50
65
39A

1

1

1
1
1
1
1

1
1
1
1
1
1
1

71
72
77

78

79A
80
81
82
83
84
85
87
94
99

Control Panel (

)

Overheat Limit Switch Otter V10c
Timer Unit - Sangamo 918801
(WARMPLAN XX AUTO)
Timer Clock Cover
(

 AUTO)

Thermostat Ranco CA6P1916
Control Panel (

 AUTO)

Red Neon Indicator
Amber Neon Indicator
Control Knob
Outer Case Assembly (not illustrated)
Dressing Strip
Bezel for Viewing Window
Gasket - Flue
Cable Clamp

WARMPLAN XX 

WARMPLAN XX

WARMPLAN XX

203 811
393 346
383 561

203 814

385 799
203 815
203 816
203 817
203 818
203 819
203 820
203 821
202 915
203 825

1
1

1

1
1
1
1
1
1
1
1
1
1
1

990965
820953

822125

822126
820954
997914
820956
820955
998786
998575
998982
820968
930611
820752

1
998477

998569
998788
998797
998789
998483

998578
998791
987451
999234
999542
991470
820046

42A

65

17

71

79A

94

40

28

49

29

85

26

80

83

87

50

99

35

72

39

81/82

77

32

39A

78

Summary of Contents for Bantam Ecotherm LPG

Page 1: ...features a wide range of information which may be of use to you and is available 24 hours a day It includes Manuals and guides downloads Servicing Where to buy our products Literature downloads www r...

Page 2: ...1 Instructions for Installation and Servicing FOR USE IN G B I E CAT I G20 at 20mbar 2H CAT I G30 31 at 28 37mbar 3 Warmplan XX Series AUTO G C No 35 694 56 MANUAL G C No 35 694 57...

Page 3: ...clock and thermostat an electronic system controls the heater automatically Warmplan XX G C No 35 694 57 This heater is identical to the Warmplan XX Auto except that it is not fitted with a time clock...

Page 4: ...urtains should clear the heater by 25mm 4 Ensure that there is an adequate gas supply available 5 Ensure that there is a suitable electrical supply available 6 If the heater is to be fitted with a flu...

Page 5: ...ith a piece of sealing tape Long FX3 Suitable for walls from 355mm 14 to 510mm 20 Medium FX2 205mm 8 to 355mm 14 Short FX1 125mm 5 to 205mm 8 Flues of lengths above 510mm 20 and up to 1525mm 60 are al...

Page 6: ...n the wall and that the rubber sealing ring is in place immediately behind the air intake flange Do not render over the face of the rubber sealing ring should rendering be necessary 6 If the flue term...

Page 7: ...ne end is already attached to the heater and has a mains cable clamp fitted Slacken the nut on the cable clamp slide it in the slot in the support plate at the bottom right hand side of the backplate...

Page 8: ...appliance electrically disconnected all switches ON including stats a meter set on W Ohms x 1 scale Test leads from L to N in appliance terminal strip block if meter reads 0 then there is a short cir...

Page 9: ...ntrol knob clockwise to position 6 The amber lamp will come on indicating that the ignition cycle has started After about 20 seconds the red lamp will come on The heater is now operating Check that th...

Page 10: ...intain the selected heat level 4 The gas cock below the heater should be left ON even when the heater is not in use 5 Neither clothes nor material should be draped over the louvres nor should furnitur...

Page 11: ...L BLUE When the flame is detected convection fan starts and red light comes on as well YL YELLOW BR BROWN Overheat limit switch operates Red light goes out Amber light stays on Gas fails lock out Red...

Page 12: ...E BL BLUE When the flame is detected convection fan starts and red light comes on as well YL YELLOW BR BROWN Overheat limit switch operates Red light goes out Amber light stays on Gas fails lock out R...

Page 13: ...12 WARMPLAN AUTO FUNCTIONAL FLOW...

Page 14: ...13 WARMPLAN MANUAL FUNCTIONAL FLOW...

Page 15: ...case 1 Turn off gas and electrical supplies 2 Remove the two screws located at the bottom of the dressing strip and slacken the two screws located behind the top louvre Fig 1 Pull the case away from...

Page 16: ...taining clips using pliers or similar and release the capillary tube and phial 4 Remove the nut and washer on the thermostat spindle and pull the thermostat assembly from the control bracket 5 Fit the...

Page 17: ...not damaged Re fit the screws and washers 6 Remake the electrical connections 7 To clean the fan brush the rotor blades with a soft brush until all the dust is removed The fan does not need lubricatin...

Page 18: ...t To assist re assembly the gasket may be held in position with a few spots of contact adhesive Replace the screws and washers and remake the gas connection Replace the air guide then replace the elec...

Page 19: ...il the electrical supply is broken and re made by turning the control knob to the OFF position or operating the override switch 2 If while the heater is running normally the flame fails because of Com...

Page 20: ...ctrode Assembly including Key No 40 Gasket Electrode Solenoid Valve Gasket Injector Holder Pressure Test Nipple Screw Printed Circuit Board Electrode 389 283 389 282 203 796 203 797 393 344 203 798 39...

Page 21: ...y Bentleywood Way Network 65 Business Park Hapton Burnley BB11 5ST Telephone 01282 686791 Fax 01282 686799 E mail info robinsonwilley co uk website www robinsonwilley co uk Robinson Willey is a Tradin...

Reviews: