(2) ALTERNATOR
Check the insulation resistance between the three
(Red,Blue and White) wires of the stator and the
generator body as shown in the figure right.
If there is a wire which has insulation resistance less
than 1 M
Ω
, replace the stator. Insulation failure
cause electrical leak which may result in
electrocution.
(3) CONTROL PANEL
Before checking, disconnect the inverter unit from
the control panel.
Measure the rechargeable parts (where the electric
current flows) and insulation resistance between the
live parts and the ground terminal. Measure with the
AC breaker on. If there is a spot where insulation
resistance less than 1 M
Ω
, replace the part.
Insulation failure may result in electrification, or an
electrical leak.