Settings
Display Adjustment Options
Default
Compressor
Short Cycle
Delay
The compressor short cycle
delay setting will not allow the
compressor to be turned on
for 5 minutes after it was last
turned off in order to protect the
compressor.
Next step
Prev step
The compressor short cycle
delay setting can be removed
by selecting
OFF
.
ON
Cooling
Differential
The cooling differential is factory
preset at 0.5°. This means that
whenever the room temperature
heats by 0.5° full degree from
the temperature setting, the
cooling system will turn on. If
the cooling system turns on too
often, increase the temperature
differential.
Next step
Prev step
The cooling differential
setting is adjustable from
0.2°F to 2°F.
0.5
Heating
Differential
The heating differential is factory
preset at 0.4°. This means that
whenever the room temperature
cools by 0.4° from the temperature
setting, the heating system will turn
on. If the heating system turns on
too often, increase the temperature
differential.
Next step
Prev step
The heating differential
setting is adjustable from
0.2°F to 2°F.
0.4
INSTALLER SETUP MENU
13