14
TECHNICIAN SETUP MENU
Filter Change
Reminder
Room
Temperature
Calibration
Minimum
Compressor
On Time
This feature will flash
FILT
in the
display after the elapsed run time
to remind the user to change the
filter. A setting of
OFF
will disable
this feature.
This feature allows the installer
to change the calibration of the
room temperature display. For
example, if the thermostat reads
70° and you would like it to read
72° then 2.
This feature allows the installer
to select the minimum run
time for the compressor. For
example: A setting of 4 will force
the compressor to run for at
least 4 minutes every time the
compressor turns on, regardless of
the room temperature.
You can adjust the filter change
reminder from
OFF
to 2000
hours of run time in 50 hour
increments. Tap the second
button from the top left side of
the thermostat to display the
current filter elapsed run time.
You can adjust the room
temperature display to read
3° above or below the factory
calibrated reading.
You can select the minimum
compressor run time from
OFF
,
3, 4, or 5 minutes. If 3, 4 or 5 is
selected, the compressor will
run for at least the selected
time before turning off.
OFF
OFF
0
Next step
Prev step
Next step
Prev step
Next step
Prev step
Tech Settings
LCD Will Show Adjustment Options
Default