background image

CAPILLARy CARE AND mOUNTINg

1.  Hold the capillary close to the control and carefully uncoil the 

required amount. Minimize rebending which makes the capillary 
more susceptible to breakage.

2.  DO NOT cut the capillary or bulb. Avoid sharp bends, kinks, strains 

or pinch marks in the capillary. Never allow the capillary to rest 
against sharp edges or rub against metal surfaces.

3.  Provide a drip loop in the capillary to prevent moisture from 

reaching the control and causing an electrical short.

4.  Don't immerse the excess capillary in the water bath or expose 

it to temperatures above 120°F. Avoid exposing the capillary to 
other extreme temperatures such as suction or discharge lines.

5.  Secure excess capillary in 3 inch coils to avoid damage from 

vibration or contact with electrical terminals. Sillicone adhesive 
applied between the coils will prevent rubbing.

6.  Although securing the excess capillary is important to dampen 

vibration, it is just as important to allow enough slack so the 
capillary is not taut like a banjo string.

7.  On startup of the equipment, observe the capillary for excessive 

vibration and make corrections as required.

BULB mOUNTINg

1.  Locate the bulb where the maximum build up of ice is to be 

maintained since the entire bulb must be surrounded with ice to 
stop the refrigeration system.

2.  A shorter cycle occurs when the bulb is located closer to the 

expansion device; a longer cycle results when the bulb is located 
closer to the outlet of the evaporator.

3.  Using the strip clamp (when provided) or the original mounting, 

attach the bulb to the evaporator coil at least 3 inches below the 
water surface, away from a direct path of high velocity water. 
The distance that the bulb is mounted from the evaporator coils 
determines the ice bank thickness.

TyPICAL BULB mOUNTINg

Figure 1 

Using O18 Strip Clamp

CONTROL wIRINg

1.  Disconnect electrical power to the unit. 
2.  All electrical wiring should conform to the National Electrical code 

and local regulations.

3.  DO NOT exceed the listed electrical ratings. 
4.  Use copper conductors only.
5.  Provide a drip loop in the wiring to prevent moisture from 

reaching the control.

6.  The terminals must not be bent, cut off, drilled or retapped. 

Electrical leads should not be taut; allow slack for temperature 
change and vibration.

When mounting a conduit connector to the O18 control frame, take 
care to not damage the switch or the control mechanism.
The cup washers furnished with the O18 are to be used when the 
conductor wires are directly connected to the terminals. The stripped 
end of the conductor should be made into a clockwise formed eye with 
an inside diameter to slip over the shank of the terminal screw. The 
clockwise forming will tend to wrap the eye of the conductor around 
the screw shank as it is being tightened. The cup washer, with its 
flanges outward, should be placed between the terminal and the screw 
head to capture the eye of the conductor.

Figure 2 

O18 Electrical Terminals

ELECTRICAL RATINgS

VAC

FLA

LRA

PD VA

HP

C12-1800

240

20

85

720

277

16

60

720

O18-100

120

17

102

720

240

17

102

720

3

241/600

125

Hermetic Compressor Motor

240

20

80

CHECkOUT

Inspect work to be assured that all the above steps were taken. Start 
up the unit and arrange to observe at least one full cycle.

ALTITUDE ADjUSTmENT

The ice bank control is not affected by altitude.

Customer Service Telephone 1.800.304.6563

Customer Service Facsimile 1.800.426.0804

[email protected]

Robertshaw®, Ranco®, Paragon® and Uni-Line® are 

trademarks of Robertshaw, its subsidiaries and/or 

affiliated companies. All other brands mentioned 

may be the trademarks of their respective owners.

For Technical Service

Telephone 1.800.445.8299

Facsimile 1.630.260.7294

[email protected]

www.uni-line.com

www.robertshaw.com

©2015 Robertshaw

3/15 –153108 Rev C

1531080C.indd   2

3/13/15   3:58 PM

Reviews: