R.
All zones served by a SlimZone control module should have the same basic load characteristics
(i.e., do not put 4 zones on an east exposure, and the 5th zone on a southwest exposure).
S.
All references to typical dampers refer to Enerstat model dampers.
T.
Zones 14-19 adhere to the same schedule and act as a single call for equipment. Although they
are separate physical zones they act as a single zone when communicating with the SZP
Control module. It is recommended that when considering the layout of your zone system,
zones 14-19 should be assigned to areas of low priority.
3.
COMPONENT REQUIREMENTS
3.1
BASIC SYSTEM
The basic system consists of the main SlimZone Premier Control module (SZP-3: 3 zone
module) and its supporting components.
ITEM
QUANTITY
CONSIDERATIONS
SZP-3 control module
one (1)
contains three (3) zones
DSL-520P zone thermostat
one (1) per zone
use standard nonshielded 4
conductor 18-24AWG copper wire
Motorized zone dampers
one (1) per zone (minimum)
use standard nonshielded 3
conductor 18AWG copper wire
24VAC transformers
one (1) for main module
75VA
zone dampers powered by
refer to section 3.4 for sizing
separate transformer(s)
Table 3.1: SlimZone Premier Basic Components
3.2
EXPANDER MODULE
Each SlimZone Expander module (SZEX) consists of two (2) additional zones. For each
expander module added, the following items are required:
ITEM
QUANTITY
CONSIDERATIONS
SZEX expander module
one (1)
contains two (2) zones
DSL-520P zone thermostat
one (1) per zone
use standard nonshielded 4
conductor 18-24AWG copper wire
Motorized zone dampers
one (1) per zone (minimum)
use standard nonshielded 3
conductor 18AWG copper wire
24VAC transformers
SZEX powered by SZP
N/A
zone dampers powered
refer to section 3.4 for sizing
by separate transformer(s)
Table 3.2: SlimZone Expander Module Components
Note: Expander module itself does not require a transformer as it is powered by the control
module.
SlimZone Premier
3
Summary of Contents for DSL-520P
Page 1: ...ZONE CONTROL SYSTEM INSTALLATION AND OPERATION MANUAL ...
Page 8: ...Figure 3 1 Typical System Diagram SlimZone Premier 5 AND ACCESSORIES OPTIONAL ACCESSORIES ...
Page 11: ...8 SlimZone Premier Figure 4 2 SZP Wiring Diagram ...
Page 12: ...SlimZone Premier 9 EMERGENCY ...
Page 32: ...Zone Schedule SlimZone Premier 29 ...
Page 33: ...SLIMZONE PREMIER SZP ZONE DIAGRAM 30 SlimZone Premier ...