MODEL 5318B
INSTRUCTION MANUAL
Level Tek II
, Capacitance Level Switch
909GF295
Page 17
Default Display
Setup
Calibrate
High Setpoint
Low Setpoint
Alarm Mode
LLFS***
HLFS*
HLFS**
Alarm Delay
Return Delay
Display
RAW*
CNVRTD
(11400*)
(01065**)
(26250***)
(14400*)
(1490**)
(26250***)
Setpoint Mode
Read Only
(Adj Diff*)
(Adj. Diff**)
(Control***)
Calibrate Setpoints
Adjustable
Differential*
High
Setpoint
Low
Setpoint
Alarm ++
Setpoint
Alarm +
Setpoint
Alarm -
Setpoint
Alarm --
Setpoint
Control
Setpoint
Model 5318B
Menu Tree
0-60 sec.
(05*)
(05**)
(00***)
0-60 sec.
(03*)
(03**)
(00***)
Sampling
4/sec*
2/sec
1/sec
CalibCLR
NO*
RESET
Selects the displayed value
update rate. This effectively
selects the measurement
range (250 pF, 500 pF or
1,000 pF)
Selects the displayed
variable. RAW = the input
frequency or CNVRTD =
proportional to the level.
Resets the units calibration
to the factory default values.
Time delay between the time
an alarm is detected and the
relay is de-activated.
Time delay between the time
an alarm is clears and the
relay is activated.
Select the alarm type. HLFS
= alarm above the high
setpoint. LLFS = alarm
below the low setpoint
Displays the current setpoint
value. This value is
calculated during calibration
And may be “fine tuned’
here.
Displays the current setpoint
value. This value is
calculated during calibration
And may be “fine tuned’
here.
Displays the currently
selected mode of operation.
NOTES:
1. * Denotes standard default values
2. ** Denotes low frequency default values
3. *** Denotes custom default values
Figure 4-2 Menu Tree