MODEL 5318B
INSTRUCTION MANUAL
Level Tek II
, Capacitance Level Switch
909GF295
Page 13
Pressing the [DN] pushbutton twice accesses
the ALARM++ procedure. The display will show:
Alarm++
XXXXX
– or –
Pressing the [DN] pushbutton three times will
access the Alarm+ procedure. The display will
show:
Alarm+
XXXXX
“XXXXX” represents the current measurement.
After a short period of time the bottom line of the
display will begin scrolling the message:
“
Calibrate horizontal probe in air for high
dielectric materials
”
– or –
“
Calibrate horizontal probe in air for low
dielectric materials
”
Pressing the [RT] pushbutton will enter the save
setpoint procedure. The display will show:
High SP
XXXXX
“XXXXX” represents the current measurement.
After a short period of time the top line of the
display will begin scrolling the message:
“
Fill tank to HIGH setpoint, then press
RT
”
Since the level is already at the desired setpoint
press [RT] to enter the save setpoint mode. The
display will show:
Save Sp-?
YES RT
Press the [RT] pushbutton to store the value or
the [LT] to abort. After pressing the [RT]
pushbutton the setpoint will be stored and the
display will return to the normal mode.
4.5.3.
ALARM - - AND ALARM -
These two modes are typically used with the
level in the vessel is above the horizontally
mounted probe. These procedures take the
current measured level and add a
predetermined offset to determine the setpoint.
The same value is stored into both setpoints.
This procedure is entered from the normal mode
by depressing the [DN] pushbutton twice,
followed by pressing the [RT] pushbutton once.
The display will show:
Step 1 RT
The bottom line will be scrolling the following
message:
“
Select method of setpoint calibration
”
Press the [RT] pushbutton once to enter the
methods submenu. The display will now show:
Exit
The bottom line will be scrolling the following
message:
“
Scroll down to select mode, then press
RT to enter or LT to exit
”
Pressing the [DN] pushbutton four times
accesses the ALARM - procedure. The display
will show:
Alarm-
XXXXX
– or –
Pressing the [DN] pushbutton five times will
access the Alarm - - procedure. The display will
show:
Alarm - -
XXXXX
“XXXXX” represents the current measurement.
After a short period of time the bottom line of the
display will begin scrolling the message:
“
Calibrate submerged horizontal probe
for low dielectric materials
”
– or –
“
Calibrate submerged horizontal probe
for high dielectric materials
”
Pressing the [RT] pushbutton will enter the save
setpoint procedure. The display will show:
Low SP
XXXXX