background image

robertsHaw sensinG switCH

teCHniCal speCiFiCation

material

Body

Glass-filled polycarbonate

Diaphragm

Silicone

Terminals

Copper alloy

Contacts 

Fine silver

operation

Operating Range

0.10 ″ W.C to 10.0″ W.C.

Max. Pressure Rating

14″ W.C.

Mounting

Standard: Diaphragm vertical 

Operating Temperature

-40 to +88 

°

C (-40 to +190 

°

F)

Sample Line Connections

Black: positive 

Gray: negative

Sample Medium

Air and byproducts of combustion 

that will not degrade silicone or 

polycarbonate

Product Life

100,000 cycles minimum

eleCtriCal

Electrical

Rating 

Standard

 Silver Contacts

SPDT Electrical load

 

1

10

 HP @120 to 277 VAC

28 VA pilot duty @ 24 VAC

125 VA pilot duty @ 120 VAC

SPST Electrical load

5 Amps resistive @ 24, 120 to 277 VAC

Contact Arrangement

SPDT

Electrical 

Connectors

 

standard 

quick-connect 

terminals ¼″ x 0.032 

General

Approvals

UL, CUL, CSA, CE,

Australian Gas Association

Accessories

Consult Factory

Are you reading a FAX or a COPY of this bulletin? DOWNLOAD the full-color PDF version of this and other 

literature at our website! http://www.invensyscontrols.com

Are you reading a FAX or a COPY of this bulletin? DOWNLOAD the full-color PDF version of this and other 

literature at our website! http://www.invensyscontrols.com

aDDitional Kits For HVaC 

appliCations!

the new sensing probe Kits

 contain a 7" 

universal probe with mounting hardware, 3' of 

vinyl tubing, a slip on adapter, and complete 

application instructions. Order 10-650 Today! 

The 

robertshaw

®

 air pressure sensing 

switches

 include Pneumatic Switches, Air 

Pressure Sensing Switches and Manual Reset 

Switches.  These reliable devices are designed 

to replace a wide variety of switches found 

in residential and light commercial applications.

•  All Air Switches come in a contractor kit 

that includes the hardware, replacement 

hose and an adjustment tool for easy 

installation and calibration. 

•  These switches include features such as 

factory-calibrated and factory-fixed set 

points, NEMA rated housings, manual 

resets and gold contacts.

•  Select Air Pressure Sensing Switches 

are practically insensitive to temperature 

change with an operating range of -40 °F 

to 190 °F.

Reviews: