SECTION 3: I
NSTALLATION
5
SECTION 3: INSTALLATION
Installation of the System Control and the associated
external electrical
w
iring m
u
st be completed by an
electrician q
u
alified in the installation of control
systems for heating eq
u
ipment.
3.1 Preparation
Before installing the System Control, obser
v
e the
follo
w
ing:
3.1.1
Ens
u
re that yo
u
ha
v
e a copy of the site layo
u
t
for the project that identifies clearly the separate
zones.
3.1.2
Read
Page 1, Section 1.4
caref
u
lly to ens
u
re
the correct installation materials are a
v
ailable.
3.2 Installin
g
the System Control Panel
3.2.1
Choose a mo
u
nting location for the System
Control. It is ad
v
isable to choose a
v
isible location
near the p
u
mp.
Do not mount System Control outdoors or in an
area with moisture spray, excessive moisture or
humidity. To avoid dama
g
e from possible drips,
do not mount controller directly beneath pump.
3.2.2
Remo
v
e the co
v
er of the System Control by
remo
v
ing the fo
u
r sec
u
ring scre
w
s.
3.2.3
Place the co
v
er and the hard
w
are in a safe
place for refitting after the external
w
iring connections
ha
v
e been made.
3.2.4
Position the mo
u
nting hole location of the Sys-
tem Control per
Figure 3
.
3.2.5
Remo
v
e the knocko
u
ts req
u
ired for the cond
u
it
entry into the System Control panel. The knocko
u
ts
are on the top of the system control case. If the
knocko
u
ts are req
u
ired to be on the bottom the case
can be rotated 180°.
3.2.6
When the case is rotated 180°, the LED stat
u
s
circ
u
it card needs to be rotated so that the LED's
match the
u
pright co
v
er panel. Remo
v
e the LED sta-
t
u
s circ
u
it card by sq
u
eezing each standoff gently
w
ith pliers one at a time
u
ntil it is loose. Rotate the
circ
u
it card so that it
w
ill line
u
p
w
ith the
u
pright co
v
er
and re-attach to the standoffs. The ribbon cable that
connects the LED stat
u
s circ
u
it card to the circ
u
it
card assembly
w
ill ha
v
e a t
w
ist in it. Use ca
u
tion not
to ca
u
se any creases or p
u
t any tension to the ribbon
cable
w
hen rotating the circ
u
it card.
FIGURE 3: Mountin
g
Hole Layout
3.3 Select the External Wirin
g
Dia
g
ram for the
Installation
3.3.1
Use
Page 7, Section 4
for the external
w
iring of
the b
u
rners, thermostats and press
u
re s
w
itch.
3.3.2
Use the table belo
w
to select the correct p
u
mp
external
w
iring diagram.
Roberts-Gordon LLC pro
v
ides, at
an additional
cost,
the follo
w
ing IEC contactor packages req
u
ired
for EP-100 and EP-201 208/230 V (1 Ø), EP-203 (3
Ø), EP-303 (3 Ø) and EP-301 (1 Ø) p
u
mps.
DANGER
Electrical Shock Hazard
Disconnect electric before service or
maintenance.
Control must be connected to a properly
grounded electrical source.
Failure to follow these instructions can
result in death or electrical shock.
Pump
Supply Volta
g
e
Pa
g
e Section Fi
g
ure
EP-100
120 V 1 Ø
7
4
5
EP-100
208/230 V 1 Ø
8
4
6
EP-201
120 V 1 Ø
7
4
5
EP-201
208/230 V 1 Ø
8
4
6
EP-301
120/208 - 230 V 1 Ø
8
4
6
EP-203
208 - 230 V (or 460 V) 3 Ø
9
4
7
EP-303
208 - 230 V (or 460 V) 3 Ø
9
4
7
10.0" (254 mm)
4.5" (114 mm)
4 x Ø 0.360" (9 mm)