SECTION 9: V
ENTING
21 of 31
FIGURE 18: Condensate Tee Assembly at Pump Inlet
FIGURE 19: Condensate Tee - Dischar
g
e Side
9.8 Condensate Trap and Condensate Tee
The condensate trap assembly (optional)
(P/N 01327001), sho
u
ld be installed on the inlet side
of the p
u
mp assembly,
See Page 21, Figure 18
.
It is possible to eliminate the condensate trap
assembly on the p
u
mp if the one-inch threaded hole
is pl
u
gged. This arrangement
w
ill permit drainage of
condensate thro
u
gh the p
u
mp and o
u
tside
v
ia
horizontal (pitched) discharge line.
The condensate trap assembly in the discharge line
can be eliminated if the discharge line is horizontal
thro
u
gh the
w
all and pitched do
w
n at least one inch
per foot. A condensate trap on the discharge side is
req
u
ired if there is a
v
ertical rise in the discharge line.
Description
Part Number
Tee 4" (10 cm)
01330203
Tee 6" (15 cm)
01330204
Drain Cap 4" (10 cm)
02718851
Drain Cap 6" (15 cm)
02718852
Condensate Val
v
e Assembly
01327001
20” (51 cm)