![Roberts Gorden Corayvac CRV-B Series Installation, Operation & Service Manual Download Page 30](http://html.mh-extra.com/html/roberts-gorden/corayvac-crv-b-series/corayvac-crv-b-series_installation-operation-and-service-manual_1469725030.webp)
CRV-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
22 of 85
FIGURE 21: Critical Han
g
er Placement (CORAYVAC
®
Classic)
Description
Part Number
Eyebolt T
u
rnb
u
ckle
91903202
Spring Hook 3/8"
91903301
T
u
be/Reflector Hanger, Sched
u
le 40 Pipe
02790300
T
u
be and Reflector Hanger - EF (Sched
u
le 40 Pipe)
03090103
Cast-Iron Comb
u
stion Chamber
02721200-1P
Cast-Iron Adapter
02722100
Run Len
g
th
Typical Expansion
Minimum “X” Len
g
th
50' (15 m)
±1" (3 cm)
12" (30 cm)
100' (31 m)
±2" (5 cm)
24" (61 cm)
150' (46 m)
±3" (8 cm)
36" (91 cm)
200' (61 m)
±4" (10 cm)
46" (122 cm)
250' (76 m)
±5" (13 cm)
57" (145 cm)