UHA L
OW
P
ROFILE
U
NIT
H
EATER
I
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
34
2. The automatic firing sequence will begin as
described
on Page 30, Figure 16
. The heater
will now operate automatically under the control
of the on site controls.
11.4.2 To Turn the Heater Off
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
The fan will continue to run for 90 seconds.
To restart, turn the thermostat above room
temperature.
11.5 Simple Troubleshooting
Some possible reasons for the heater not operating
are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not
"ON".
4. A limit switch may have operated. This may be
caused by an interruption of the electrical
supply, failure of the distribution fan or vent or
heat exchanger blockage.
If a temperature limit switch persistently trips, there
is a fault which must be investigated by a contractor
qualified in the installation and service of gas-fired
heating equipment.
11.5.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry
for ignition (four trials total). After four unsuccessful
ignition trials, the control will put the heater into
lockout for one hour.
Lockout should not occur during normal operation of
the heater and indicates there is a fault condition
which must be corrected. There is an LED light on
the ignition control that flashes codes to assist in
fault correction.
See Page 34, Figure 20
for LED
indication codes.
Figure 20: LED Diagnostic Codes
LED INDICATION FAULT MODE
Slow Flash
Normal Operation - No call for heat.
Fast Flash
Normal Operation - Call for heat.
2 Flashes
Ignition Lockout - No flame detected.
3 Flashes
Airflow Fault - Pressure switch open or closed.
4 Flashes
Temperature Limit or
Manual Reset Limit Switch Open
5 Flashes
Flame Sense Error - Gas valve not energized.
Steady On
Internal Control Failure