![Roberts Gorden Combat CTCU 11 Operation And Service Manual Download Page 33](http://html.mh-extra.com/html/roberts-gorden/combat-ctcu-11/combat-ctcu-11_operation-and-service-manual_1469612033.webp)
SECTION 15: R
EMOVAL
AND
R
EPLACEMENT
P
ARTS
27
15.2 Burner Compartment
15.2.1 Burner Injectors
Remove flexible
air duct from spigot.
Viewing Port
Flame Probe
Burner
Compartment
Cover
Ignition Electrode
Remove screws and
pull off burner cover.
The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the gas
pipe rubber seal fully in place and all
screws fitted and tight.
MODEL
CTCU-7
CTCU-11
CTCU-15
CTCU-22
CTCU-27
CTCU-32
Injector Quantity
2
3
4
5
6
7
Natural Gas (G20)
Injector size mm Ø
1.78
1.85
1.85
2.06
2.057
2.057
in Ø
0.070
0.073
0.073
0.081
0.081
0.081
Marking
50
49
49
46
46
46
RG P/N
91930050
91930049
91930049
91930046
91930046
91930046
Natural Gas (G25)
Injector size mm Ø
1.99
2.06
2.06
2.26
2.261
2.261
in Ø
0.0785
0.081
0.081
0.089
0.089
0.089
Marking
47
46
46
43
43
43
RG P/N
91930047
91930046
91930046
91930043
91930043
91930043
LPG Propane (G31) and LPG Butane (G30)
Injector size mm Ø
1.18
1.18
1.18
1.25
1.25
1.25
in Ø
0.0465
0.0465
0.0465
0.049
0.049
0.049
Marking
56
56
56
1.25
1.25
1.25
RG P/N
91930056
91930056
91930056
91930125
91930125
91930125
Remove manifold
screws and pull
out manifold.
Manifold
Burners
Injectors
Manifold
Mounting
Bracket
Gromet
Unscrew
Injectors
Manifold
Marking
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.