Roberts Gorden bzc 700 Operation Manual Download Page 10

4.3.5

The screen will now show:

Enter end time 1700.

The screen will now show:

Press ENTER.

4.3.6

The screen will now show:

Press ENTER, to skip without altering the
setting.
The reason for leaving the start and end
times blank is because in this example we
are only using one switching period per day.
Repeat as above for periods 3 and 4 for
Monday.

4.3.7

The screen will now show:

Pressing the PROG key at this point will copy
all of Monday’s switching times to Tuesday.

4.3.8

The screen will now show:

Pressing the PROG key at this point will copy
the times from Tuesday to Wednesday.
Repeat this for Thursday and Friday.

4.3.9

The screen will now show:

For Saturday, the switching period is different
from the weekday settings. The new settings
must be entered.

Enter start time 0800, Press ENTER.

The screen will now show:

Enter end time 1200.

The screen will now show:

Press ENTER.
Leave the start and end times blank for peri-
ods 2, 3 and 4 because in this example we
are only using one switching period on
Saturday.

As no switching times are required for
Sunday, press RUN to save the settings and
return to the menu.

The process described above must now be
repeated for each heating zone to be altered.

4.3.10

If any mistakes were made during the pro-
gramming sequence, see 

Page 5, Section

4.1 for corrective action.

4.3.11

Press RUN to return to Normal (Run) Mode.

NOTE:

If remote time enable is to be used, leave all
switching periods set to 00.00.

4.4

MANUAL OVERRIDE TEMPERATURE

4.4.1

To manually override temperature, first use
the left and right arrow keys to display the
zone you wish to alter.

Example for zone 1 is shown below:

The set point temperature appears in the
brackets.

4.4.2

Pressing the UP and DOWN ARROW KEYS
will increase or decrease the set point (in
increments of 1

O

) for the displayed zone with-

in pre-set limits.

NOTE:

Changing the set point for the daytime tem-
perature manually will only apply to the cur-
rent switching period.

4.5

MANUAL OVERRIDE TIME

4.5.1

From the Normal (Run) Mode, press the
OVERRIDE key to enter the override pro-
gram. Enter a security code if prompted.

Override will allow the heating system to be
switched to day or night mode manually.

4.5.2

The screen will now show:

Select the zone required to be overridden.

6

ROBERTS GORDON

®

BZC

700 

OPERATION MANUAL

ENTER SWITCHING TIMES FOR PERIOD 1 MON
START:

08.00

END:

00.00

ENTER SWITCHING TIMES FOR PERIOD 1 MON
START:

08.00

END:

17.00

ENTER SWITCHING TIMES FOR PERIOD 2 MON
START:

00.00

END:

00.00

ENTER SWITCHING TIMES FOR PERIOD 1 TUE
START:

00.00

END:

00.00

ENTER SWITCHING TIMES FOR PERIOD 1 WED
START:

00.00

END:

00.00

ENTER SWITCHING TIMES FOR PERIOD 1 SAT
START:

00.00

END:

00.00

ENTER SWITCHING TIMES FOR PERIOD 1 SAT
START:

08.00

END:

12.00

ENTER SWITCHING TIMES FOR PERIOD 1 SAT
START:

08.00

END:

00.00

HEATING ZONE NO1

(20)

:

17

STATUS:DAY

HEAT ON

PLEASE ENTER THE NUMBER OF THE ZONE YOU

WISH TO OVERRIDE (1-7)

Summary of Contents for bzc 700

Page 1: ...Installation must be done by an electrician qualified in the installation of control systems for heating equipment Improper installation adjustment alteration service or maintenance can result in death injury or property damage Read the installation and operation manuals thoroughly before installing or servicing this equipment Installer Please take the time to read and understand these instruction...

Page 2: ......

Page 3: ... 6 4 6 Holiday Periods 7 4 7 Holiday Mode 7 4 8 Change the Current Time and Date 7 4 9 Seasonal Time Adjustment 8 4 10 How to Enter Zone Titles 8 4 11 How to Clear Memory 8 4 12 Changing the Security Code 8 4 13 Changing the Override Limits 9 5 The ROBERTS GORDON BZC 700 Controller Warranty 10 u uTABLE OF FIGURES Figure 1 Keypad Layout 2 Figure 2 ROBERTS GORDON BZC Controller Quick Programming Gui...

Page 4: ......

Page 5: ...1 3 SAFETY Your Safety is Important to Us This symbol is used throughout the man ual to notify you of possible fire electrical or burn hazards Please pay special attention when reading and following the warnings in these sections For optimum heater performance and safe heating conditions inspect and maintain heater s before every heating season and as necessary Also know and maintain heater cleara...

Page 6: ...ve Battery Back up Lithium cell maintains data memory and time clock for 10 years minimum at 77 F 25 C 2 3 PRESET DEFAULT FACTORY SETTINGS Temperature Settings Day Temperature 20 C Night Temperature 04 C Override Up Temperature 02 C Override Down Temperature 04 C Time Settings Switching Times NONE Override Limit 8 hours Maximum Pre heat Hours 3 hours Date Format dd mm yy Optional Settings HILO Swi...

Page 7: ...he required DAY temperature 2 OFF heating in the zone will be in the NIGHT set back condition 3 5 Enter the number of hours you wish to override e g 01 The preset maximum number of hours is displayed in brack ets 3 6 Press ENTER 3 7 When selection is complete scrolling to the next screen using the scroll key in run mode will activate the override 3 8 To end override before the set time is reached ...

Page 8: ... to Normal Run Mode 3 3 HOURS RUN Press PROG and enter the code 1805 Press ENTER Enter 5 for HOURS RUN By selecting the hours run mode the record ed running hours for the previous four weeks for each relay can be viewed Enter the relay number to be viewed the subsequent display will be as follows Press ENTER to return to selection screen To view another zone repeat the steps above Press RUN to ret...

Page 9: ...R 4 2 4 The screen will now display switching times If you wish to alter switching times go to Page 5 Section 4 3 2 4 2 5 To accept the settings and return to the DATA menu press RUN 4 2 6 To alter the set points for further zones repeat the steps on Page 5 Sections 4 2 1 to 4 2 3 4 2 7 If any mistakes were made during the pro gramming sequence see Page 5 Section 4 1 for corrective action When all...

Page 10: ...ormal Run Mode NOTE If remote time enable is to be used leave all switching periods set to 00 00 4 4 MANUAL OVERRIDE TEMPERATURE 4 4 1 To manually override temperature first use the left and right arrow keys to display the zone you wish to alter Example for zone 1 is shown below The set point temperature appears in the brackets 4 4 2 Pressing the UP and DOWN ARROW KEYS will increase or decrease th...

Page 11: ...y be used to correct mis takes Press ENTER when correct 4 6 4 If any mistakes were made during the pro gramming sequence see Page 5 Section 4 1 for corrective action 4 6 5 Press RUN to return to Normal Run Mode NOTE If ENTER is pressed at any display then the current setting will be retained NOTE To cancel a holiday period in progress repeat 4 6 1 to 4 6 3 changing the period in progress to 00 len...

Page 12: ...ramming sequence see Page 5 Section 4 1 for corrective action 4 11 HOW TO CLEAR MEMORY This facility will clear the logs of the hours run and monitor data 4 11 1 Press PROG and enter the code 1805 Press ENTER Enter 6 for CLEAR MONITOR 4 11 2 The screen will now show Press the DEL key and a prompt for the passcode will appear Pressing any other key will abort the process 4 11 3 The screen will now ...

Page 13: ... installer 4 13 3 The screen will now show The default maximum override of 8 hours is displayed To alter the number enter the new number and press ENTER 4 13 4 The screen will now show The default upper offset limit of 2O Centegrade is displayed To alter the number enter the new number and press ENTER 4 13 5 The screen will now show The default upper offset limit of 5O Centigrade is displayed To a...

Page 14: ......

Page 15: ...S VOID IF The ROBERTS GORDON BZC 700 Controller is not installed by a suitably qualified electrician The Customer cannot prove original purchase date and required annual maintenance history Any data plate and or serial number on the ROBERTS GORDON BZC 700 Controller is removed defaced modified or altered in any way The ROBERTS GORDON BZC 700 Controller is transferred This warranty is non transfera...

Reviews: