5

RND 305-00016 & 305-00017

ENGLISH

Stage 1.   THE I-PHASE. The constant current charging, Bulk LED is on.

Normally the batt ery is charged at constant maximum current until it rises to the selected Absorption voltage level.

The charging voltage changes with the batt ery voltage.

If the initial batt ery voltage is less than 9V due to deep discharge, the bulk charge current is reduced to half of the maximum  

until batt ery voltage rises over 9V.

Stage 2.   THE UO-PHASE. The constant voltage charging, Absorption LED is on .

Batt ery Type Selection: Gel: 14.1V / Wet: 14.4V / Calcium: 15.5V

When the batt ery voltage rises to the selected Absorption voltage level, the charging switches to Constant voltage  

charging and batt ery is over 85% full. The batt ery is kept at this high voltage while the current reduces gradually to set value  

at which the charger automatically switches to Float Stage.

Stage 3.   THE UO-PHASE. The constant voltage charging, Float LED is on.

Float Voltage Selection: 13.2 V / 13.5V / 13.8V

In this stage, the batt ery is full and only takes in the amount of current necessary for maintaining the capacity. The fl oat  

voltage is preset independently by user according to the type of batt ery such that batt ery can be connected permanently to  

the charger when it is not in use.

E. Manual Equalization Charging for wet type batt ery only

Wet lead acid batt ery requires periodic high voltage charging (about 10% overcharge absorption voltage) to balance the  

voltage of each cell, reverse the high concentration of electrolyte at the bott om and clear up large sulfate crystals on the  

plates. You can use the Calcium–Calcium selection to perform the manual equalization by carefully following the 

batt ery maker’s recommended frequency and duration.

Make sure to manually switch off  charger when time is up.

Take special precautions as batt ery will emit explosive gas during equalization charge.

F. Dual bank charging ( RND 305-00016 )

This feature is for caravans, and vehicles with two separate batt eries.

The two batt eries must be of same chemical make up and type to avoid over and under charging because only one sett ing of  

charging profi le for both.

Two batt eries are charged simultaneously and the batt ery with the lowest level gets most share of the current in the Bulk  

charge stage until it is up to the same voltage level of the second batt ery (batt ery with higher initial level).

Both batt eries will go to the Absorption and the Float Charge at the same time.

G. Power Supply / 2-Stage Charger Mode (see Fig.3)

At this mode the Charger On (5) LED becomes red color and only Bulk and Float LED will function. The bulk LED will be off   

when batt ery is charged to about 80% full.

The 3-stage charger becomes a 2-stage charger or as power supply in this selected mode because 3-stage charger over 

charges batt ery with external load.

This selected mode is intended for use to charge batt ery with external load such as caravan or other batt ery and external  

load combination.

A 2-Stage charger can be used as a combination charger/power supply. An external load can draw current from the charger  

while the charger is recharging a batt ery. The charger does not care how much current is being diverted by an external 

circuit as it switches from Bulk mode (constant current ) to Float mode based only on the batt ery terminal voltage.

However, a 2-Stage charger cannot completely charge the batt ery when the charger switches from bulk mode to fl oat mode.

Aft er switching to fl oat mode, the batt ery will, in most cases, be about 80% recharged. The batt ery receives the remaining  

recharge while in fl oat mode over several days.

It is highly recommended to switch back to the 3-Stage Charger Mode periodically when the external load is disconnected.

Also the external load should not be more than 50% of the max. current of the charger , unless the batt ery is fully charged  

up . If the bulk LED is on most of the time then the load is too large.

G1. As a stand alone power supply

It can also be used as a stand alone power supply without connection to a batt ery

It will provide a constant voltage according to the selected Float Voltage (13.2/13.5/13.8V) and rated DC current of the    

charger.

However, it is not recommended for high surge load (such as lamp) in stand alone application as the initial high surge current  

will trigger the overload protection of the power supply.

Summary of Contents for 305-00016

Page 1: ...1 RND 305 00016 305 00017 USER MANUAL BEDIENUNGSANLEITUNG 3 Stage Batt ery Charger RND 305 00016 305 00017...

Page 2: ...eable parts inside Do not charge the battery on boats Remove the battery and charge on shore Never attempt to charge a frozen battery Never attempt to charge a damaged battery Wear protective goggles...

Page 3: ...Charger 2 Battery Charger Power Supply Selection Slide Switch to set Charger to 3 Stage Charger or Power Supply Mode See Section G 3 Battery Type Selection Slide Switch to set charger for AGM Gel Wet...

Page 4: ...charger in a well ventilated place make sure the mounting surface is at and without soft covering material or loose paper sheet The air intake is at the bottom and air outlet at the back Make sure bo...

Page 5: ...under charging because only one setting of charging pro le for both Two batteries are charged simultaneously and the battery with the lowest level gets most share of the current in the Bulk charge st...

Page 6: ...6 RND 305 00016 305 00017...

Page 7: ...ght cable size cable integrity Recheck battery type and change to correct battery selection Make sure charger rating matches battery capacity see table B2 Move battery to a room temperature location o...

Page 8: ...Charge Protection Type Constant Current Limiting recovers Automatically after Fault Condition is Removed Short Circuit Recovers Automatically After Fault Condition is Removed Reverse Polarity Car Bla...

Page 9: ...9 RND 305 00016 305 00017 USER MANUAL BEDIENUNGSANLEITUNG 3 Phasen Batt erieladeger t RND 305 00016 305 00017...

Page 10: ...ngen Sie die Batterie zum Laden an Land Versuchen Sie auf keinen Fall eine gefrorene Batterie zu laden Versuchen Sie auf keinen Fall eine besch digte Batterie zu laden Tragen Sie beim Anschliessen ode...

Page 11: ...mversorgung des Ladeger ts 2 Auswahl Ladeger t Netzteil Schiebeschalter zum Einstellen des Ladeger ts auf 3 Phasen Ladeger t oder Netzteilmodus Siehe Abschnitt G 3 Auswahl des Batterietyps Schiebescha...

Page 12: ...Der Lufteinlass be ndet sich an der Unterseite der Luftauslass an der R ckseite des Ladeger ts Vergewissern Sie sich dass der Luft Einlass und Auslass v llig unbehindert ist Platzieren Sie das Ladeger...

Page 13: ...g aufweisen und demselben Typ angeh ren um ein ber oder Unterladen zu vermeiden da eine einzige Einstellung des Ladepro ls f r beide Ladebanken verwendet wird Die zwei Batterien werden gleichzeitig au...

Page 14: ...14 RND 305 00016 305 00017...

Page 15: ...tand pr fen Batterietyp erneut pr fen und richtigen Typ ausw hlen Sicherstellen dass das Modell des Ladeger ts f r die Batteriekapazit t geeignet ist siehe Tabelle B2 Die Batterie an einen Ort bringen...

Page 16: ...angsstroms Softladung Schutzklasse Konstantstrombegrenzung automatische Wiederherstellung nach Beseitigung des Fehlerzustands Kurzschluss Automatische Wiederherstellung nach Beseitigung des Fehlerzust...

Reviews: