background image

M2A-XL Transmitter Operator’s Manual

Chapter 5: Configuration Mode

 • 

47

Chapter 5: Configuration Mode

Overview

This chapter describes how to view and change M2A-XL parameters using Configuration Mode. 
It is accessed using the program buttons.

Configuration Mode includes a 5-minute time-out feature. If you do not press a control button for 
5 minutes, the M2A-XL automatically returns to normal operation.

NOTE:

If the M2A-XL returns to normal operation because of a time-out, it enters a warm-up 
period just as it does when it is first turned on.

If you are installing a new M2A-XL, it has been setup at the factory. Use Configuration 
Mode only if you want to change the M2A-XL’s setup. If you want to change the 
detector type see “Chapter 6: Gas Type Mode” on page 51.

Viewing & Changing M2A-XL Parameters

1. While in normal operation, simultaneously press and hold the UP/YES and ENTER buttons 

for 5 seconds to enter Configuration Mode. Release the buttons when the following screen 
appears.

2. If you want to exit Configuration Mode, press and release the DOWN/NO button and the 

M2A-XL will return to normal operation.
If you want to continue in Configuration Mode, press and release the UP/YES button. The 
target gas and the full scale will be displayed for a few seconds before the first adjustable 
parameter, the alarm 1 setpoint, is displayed.

3. If you want to change the currently displayed parameter, use the UP/YES and DOWN/NO 

buttons to adjust it to the desired setting, then press ENTER to continue to the next parameter.
If the currently displayed parameter is OK, press the ENTER button to proceed to the next 
parameter.
Table 11 lists the M2A-XL parameters you can set. Table 11 also lists the factory set value 
for each parameter.

Enter

Config?

Summary of Contents for M2A-XL

Page 1: ...RKI Instruments Inc www rkiinstruments com M2A XL Transmitter Operator s Manual Part Number 71 0610 Revision P1 Released 10 20 22...

Page 2: ...Periodic calibration and maintenance of the gas monitor is essential for proper operation and correct readings Please calibrate and maintain this instrument regularly Frequency of calibration depends...

Page 3: ...cates the full extent of our liability and we are not responsible for removal or replacement costs local repair costs transportation costs or contingent expenses incurred without our prior approval TH...

Page 4: ...2A XL Transmitter 25 Wiring the M2A XL Transmitter 30 Start Up 38 Chapter 4 Operation 41 Overview 41 Normal Operation 41 Information Screen 41 4 20 mA Signal Output Operation 42 Alarm Indications 43 C...

Page 5: ...485 Modbus Output 73 Overview 73 Wiring the M2A XL in a Modbus System 73 Using the M2A XL in a 4 wire Modbus System 77 Modbus Mode 77 Supported Modbus Functions 79 Chapter 9 Parts List 85 Appendix A C...

Page 6: ...visible through the window in the cover front face and provides a 4 20 mA signal which indicates the target gas reading for use by a gas monitoring controller recording device or programmable control...

Page 7: ...en Oxygen O2 0 25 0 volume 0 1 increments CO H2S Carbon Monoxide CO 0 300 ppm 1 ppm increments Carbon Monoxide CO 0 200 ppm 1 ppm increments Carbon Monoxide CO 0 100 ppm 1 ppm increments Hydrogen Sulf...

Page 8: ...50 ppm 1 00 ppm Combustible Gas LEL 10 LEL 50 LEL Combustible Gas 0 100 Volume 100 100 Hydrogen Cyanide 5 0 ppm 10 0 ppm Hydrogen Sulfide 0 50 ppm 5 0 ppm 10 0 ppm Hydrogen Sulfide 0 100 ppm 10 ppm 5...

Page 9: ...7 Series N A 20 C to 40 C Infrared Combustible 20 C to 50 C 40 C to 50 C Infrared CO2 20 C to 50 C 40 C to 50 C Accuracy Catalytic Combustible Gas LEL range 5 of reading or 2 LEL whichever is greater...

Page 10: ...4 NPT conduit ports to mount the detector to the junction box factory installed in the bottom port and connect wiring from an external device left port The top port is shipped with a factory installe...

Page 11: ...ctor senses the target gas and is mounted in a 3 4 NPT conduit port on the right bottom side of the M2A XL A variety of detectors may be used with the M2A XL See the sections below for descriptions of...

Page 12: ...ed IR detectors Table 3 Infrared IR Detectors Target Gas Range M2A XL Part Number Detector Used CH4 0 100 LEL 65 2649RK CH4 61 0190RK CH4 UL 65 2664RK CH4 61 0197RK CH4 CH4 0 5 00 volume 65 2649RK CH4...

Page 13: ...entire oxygen detector must be removed if replacement is required for the 65 2510RK CO2 0 50 volume 65 2660RK 05 61 0191RK 05 UL 65 2661RK 05 61 0198RK 05 CO2 0 100 volume 65 2660RK 10 61 0191RK 10 U...

Page 14: ...ence between the 65 2428 and the 65 2428 01 is that the sensor used in the 65 2428 01 is resistant to degradation caused by frequent exposure to low levels of H2S or occasional exposure to high levels...

Page 15: ...05 65 2438 CSA 65 2663RK 65 2496RK CO 0 200 ppm 65 2646RK 05 02 65 2438 01 CO 0 100 ppm 65 2646RK 05 01 65 2438 01 H2S 0 100 ppm 65 2645RK 05 65 2428 CSA 65 2645 05 07 65 2428 01 CSA 65 2662RK 65 249...

Page 16: ...e the splashguard to allow access to the sensor that protrudes through the detector housing cap You can then push the appropriate ESM 01 calibration cup onto the sensor The table below outlines the M2...

Page 17: ...s for the CT 7 Series detectors Table 7 CT 7 Series Detectors Target Gas Range M2A XL Part Number Detector Used Cl2 0 3 ppm 65 2670 CL2 3 65 2302 CL2 3 Cl2 0 5 ppm 65 2670 CL2 5 65 2302 CL2 5 Cl2 0 10...

Page 18: ...670 NH3 2 65 2302 NH3 2 NH3 0 500 ppm 65 2670 NH3 5 65 2302 NH3 5 SO2 0 10 ppm 65 2670 SO2 10 65 2302 SO2 10 Table 7 CT 7 Series Detectors Target Gas Range M2A XL Part Number Detector Used Hydrophobic...

Page 19: ...hree standoffs and rests on a thin layer of foam A banana jack is screwed into each of the standoffs and is used for mounting the control PCB The terminal PCB converts the electrical output from the d...

Page 20: ...t Figure 10 Terminal PCB Component Location Power Signal Terminal Strip The power signal terminal strip is a three position plug in style terminal strip located at the top of the left terminal column...

Page 21: ...l strips consists of from top to bottom the fail alarm 1 and alarm 2 relay terminal strips They are three position plug in style terminal strips The relay terminal strips are used to connect devices s...

Page 22: ...g standoffs and pushing it onto the banana jacks The jacks retain the control PCB Figure 12 Control PCB Component Location OLED Display The OLED display is located at the top of the control PCB It ind...

Page 23: ...is not possible to actuate two magnetic switches at once with only one magnetic wand Since displaying the Information Screen only requires the use of one switch the wand may be used to show the Inform...

Page 24: ...alarm 1 LED is on when the M2A XL is experiencing an alarm 1 condition Alarm 2 LED The alarm 2 LED is on when the M2A XL is experiencing an alarm 2 condition RX TX LED s These LED s indicate data bein...

Page 25: ...m start up maintenance and calibration procedures Select a site where the target gas is likely to be found first For lighter gases mount the detector near the ceiling for heavier gases mount the detec...

Page 26: ...nsions Catalytic LEL and ppm CSA Version Figure 15 Outline Mounting Dimensions IR Combustible CO2 3 4 NPT Conduit Port Plugged 2 3 max 1 00 4 86 3 4 NPT Conduit Port 0 25 2X 5 5 5 66 2 82 6 2 7 8 max...

Page 27: ...Outline Mounting Dimensions Replaceable Sensor H2S CO and Oxygen Non Explosion Proof 3 4 NPT Conduit Port Plugged 1 1 2 20 For Calibration Cup 2 6 max 1 00 4 86 3 4 NPT Conduit Port 0 25 2X 5 5 5 66...

Page 28: ...n Startup M2A XL Transmitter Operator s Manual Figure 18 Outline Mounting Dimensions H2S CO and Oxygen CSA Explosion Proof 3 4 NPT Conduit Port Plugged 1 00 3 4 max 3 4 NPT Conduit Port 0 25 2X 5 5 5...

Page 29: ...itter Operator s Manual Chapter 3 Installation Startup 29 Figure 19 Outline Mounting Dimensions ESM 01 Toxic 3 4 NPT Conduit Port Plugged 4 82 max 1 00 4 86 3 4 NPT Conduit Port 0 25 2X 5 5 5 66 2 82...

Page 30: ...are not to pull too hard and damage the cable which connects the control and terminal PCBs 4 Let the control PCB hang by the cable The terminal strips are now visible on the terminal PCB The control P...

Page 31: ...L R white wire to terminal labeled LEL W green wire to terminal labeled LEL G black wire to terminal labeled LEL B Figure 21 Catalytic LEL and ppm Detector Wiring Figure 22 IR Combustible IR CO2 Detec...

Page 32: ...labeled OXY Figure 23 Partial Pressure Oxygen Detector Wiring Figure 24 CSA Capillary Type Oxygen Detector Wiring Figure 25 Capillary Type Replaceable Sensor Oxygen Detector Wiring Green White C NC NO...

Page 33: ...TOXIC Figure 26 H2S CO Detector Wiring CSA Non Explosion Proof CO or H2S Gas Detectors Red wire to terminal labeled TOXIC black wire to terminal labeled TOXIC Figure 27 H2S CO Detector Wiring Black R...

Page 34: ...lor coded wire Connect the color coded wire see chart below to the terminal labeled TOXIC and the black wire to the terminal labeled TOXIC Figure 28 ESM 01 Toxic Detector Wiring Black Brown AsH3 Yello...

Page 35: ...ge to the terminal strip The detector terminal strip and the alarm 1 relay terminal strip may be removed by grasping them with your fingers if the adjacent terminal strips have been removed WARNING If...

Page 36: ...onduit port is used for wiring be sure to seal the threads to ensure water does not enter the junction box A conduit seal which is normally required to maintain the junction box s hazardous location r...

Page 37: ...ctions Make sure any wire or cable used for relay wiring is appropriately rated for the power that it will carry NOTE If shielded cable is used for the PWR SIG connections leave the cable shield s dra...

Page 38: ...that all wiring connections are correct and secure 3 Turn on the incoming power 4 If necessary turn on the controller or other monitoring device that is connected to the M2A XL 5 The OLED display will...

Page 39: ...t do not remove the junction box cover Use the magnetic wand accessory to actuate the magnetic switches instead of pushing the control switch buttons To actuate a magnetic switch and perform the same...

Page 40: ...Cal Gas 5 Press and release the DOWN NO button The display will indicate Leaving CAL Mode and the M2A XL will return to normal operation Oxygen Version Adjusting the Fresh Air Reading 1 While in norma...

Page 41: ...M2A XL Information Screen The Information Screen displays the M2A XL s operating voltage and firmware and hardware information To display the Information Screen do the following 1 Press and hold the...

Page 42: ...ration is performed In this situation the signal output will be fixed at 3 5 mA for LEL and toxic versions and 17 4 mA for oxygen versions from the time Gas Type Mode is entered until the M2A XL is ca...

Page 43: ...for O2 gas reading at or above the alarm 1 set point A1 LED is on Gas reading alternates with ALARM 1 message Alarm 2 Increasing gas reading at or above the alarm 2 setpoint A2 LED is on Gas reading...

Page 44: ...s the alarm 1 relay NOTE If the ENTER button is pressed while the M2A XL is in an alarm 1 condition the A1 LED will flash but all other indications will remain unchanged You cannot de energize the ala...

Page 45: ...il condition for any of the following The detector wiring is disconnected or incorrectly connected The plug in sensor is not properly plugged into the socket in the detector housing body NOTE It could...

Page 46: ...input voltage is displayed on the bottom line of the OLED display The fail relay de energizes NOTE The low power alarm cannot be cleared using the ENTER button When the voltage increases to 10 0 volts...

Page 47: ...Changing M2A XL Parameters 1 While in normal operation simultaneously press and hold the UP YES and ENTER buttons for 5 seconds to enter Configuration Mode Release the buttons when the following scree...

Page 48: ...tiated It can be set in 1 sec ond increments from 0 60 seconds in 1 minute increments from 1 15 minutes and in 15 minute increments from 15 60 minutes A1 OffDy alarm 1 off delay 0 sec The amount of ti...

Page 49: ...ng For example if the zero suppression setting for a combustible LEL detector is 2 0 LEL the M2A XL will display a reading of 0 LEL for gas readings from 2 LEL to 2 LEL It is setta ble from 0 to 6 of...

Page 50: ...YES button to return to normal operation If you wish to change some of the adjustments made press and release the DOWN NO button The DO OVER YES NO message will display Press and release the UP YES b...

Page 51: ...d on Selecting the Gas Type 1 While in normal operation or during the warm up sequence press and hold the UP YES and DOWN NO buttons for five seconds Release them when the following screen appears 2 I...

Page 52: ...the highest displayed value Anything higher is displayed as OVER Table 13 Toxic Oxygen Gas Types Gas Type Choices Detection Range H2S 0 100 ppm CO 0 300 ppm CO 0 200 ppm CO 0 100 ppm CL2 0 3 00 ppm C...

Page 53: ...meter setting and move to the next one Use the UP YES and DOWN NO buttons to adjust a setting See Chapter 5 Configuration Mode on page 47 for a complete description of Configuration Mode 7 When you ha...

Page 54: ...e after changing the gas type 11 See Calibration Combustible Gas CO2 and Toxic Versions on page 58 or Calibration Oxygen Version on page 63 for calibration instructions NOTE When calibrating an M2A XL...

Page 55: ...formance of the M2A XL It includes daily quarterly and biannual procedures Daily Verify a display reading of zero 20 9 for an oxygen M2A XL Investigate significant changes in the reading Quarterly Cal...

Page 56: ...continue contact RKI for further instruction Frequent or Suspect Alarms The M2A XL alerts you to frequent or suspect alarms while the fresh air readings remain on zero 20 9 for oxy gen The M2A XL is e...

Page 57: ...n the detector housing cap is blocked with dirt of some other particulate contamination For CT 7 Series detectors The hydrophobic membrane on the plug in sensor face is blocked with dirt or some other...

Page 58: ...ncy of every 6 months for a non IR M2A XL or 12 months for an IR M2A XL is adequate If an application is very demanding for example if a combustible or toxic gas is present often and in significant co...

Page 59: ...of the magnetic wand to the M2A XL s glass cover directly above the magnetic switch you wish to actuate Touching the glass and removing the wand is the same as pressing and releasing a button Touchin...

Page 60: ...ClO2 be sure the M2A XL has been on for 15 minutes before performing a calibration For ClO2 be sure the M2A XL has been on for 2 3 hours before performing a calibration WARNING RKI Instruments Inc re...

Page 61: ...inder into the fixed flow regulator 5 Turn the regulator knob counterclockwise to open the regulator 6 Allow zero air to flow for two minutes If there was gas present causing a reading on the M2A XL t...

Page 62: ...he calibration cup from the detector For an ESM 01 detector pull the calibration cup off of the ESM 01 sensor and screw the splashguard back onto the detector housing cap The M2A XL will continue to d...

Page 63: ...s will remain in their non alarm state while the M2A XL is in Calibration Mode The output signal will not indicate current readings and the relays will not resume operating normally until the M2A XL i...

Page 64: ...sh air adjustment the M2A XL will freeze the display reading at the highest response and the M2A XL will continue to display this reading and retain it in its memory until the fresh air adjustment pro...

Page 65: ...to continue with adjusting the zero setting press and release the UP YES button APPLY will alternate with ZERO Gas on the top display line and the current oxygen reading will be on the bottom display...

Page 66: ...placing Components of the M2A XL Replacing the Gas Detector NOTE For M2A XL versions that do not have a replaceable plug in sensor or if you determine that it is necessary to replace the entire detect...

Page 67: ...replacement detector leads through the bottom conduit port of the junction box then screw the mounting threads of the detector into the conduit port If necessary for environmental conditions apply thr...

Page 68: ...if necessary Be sure the ribbon cable is routed down below the control PCB so it will not be damaged by the cover when it is screwed back on 13 Secure the junction box cover to the junction box 14 Tur...

Page 69: ...not removed Figure 31 Plug In Sensor Jumper Removal 6 If you are replacing a CO sensor install the rubber boot and charcoal filter onto the new sensor s face If you are replacing the 65 2428 explosio...

Page 70: ...sure that the cap gasket is in place and screw the detector cap back onto the housing body 6 Turn on or reconnect power to the M2A XL Replacing an Oxygen Plug in Sensor NOTE This procedure is applicab...

Page 71: ...If the splash guard was unscrewed from the detector cap screw it back onto the detector cap 7 Turn on or reconnect power to the M2A XL NOTE Allow the replacement sensor to warm up for 15 minutes befor...

Page 72: ...the white hydrophobic membrane from the sensor face with a small flat blade screwdriver or a similar tool 5 Peel off the hydrophobic membrane It may be necessary to clean off the sensor face to remov...

Page 73: ...n be found online at www modbus org specs php The Modbus protocol supports a maximum of 247 unique slave addresses 1 247 The M2A XL s line driver provides for up to 128 M2As to be connected together w...

Page 74: ...uration 5 wires are used for wiring the M2A XL into a Modbus system Figure 32 also illustrates typical alarm device wiring The ground jumper must be removed in this wiring configuration Figure 32 Reco...

Page 75: ...bus controller is omitted Instead the Common terminal on the Modbus controller is connected to the of the 24 VDC power supply The ground jumper must be installed in this wiring configuration Figure 33...

Page 76: ...ination jumper removed see Figure 34 Figure 35 below Figure 34 Multiple M2As in a Daisy Chain Configuration Figure 35 Multiple M2As in a Two Branch Configuration Modbus Master Up to 128 M2As can be co...

Page 77: ...XL automatically returns to normal operation NOTE If the M2A XL returns to normal operation because of a time out it enters a warm up period just as it does when it is first turned on 1 While in norm...

Page 78: ...to normal operation NOTE All M2As on a Modbus network must be configured with the same baud rate and parity and each M2A XL must have a unique slave ID For an M2A XL to participate on a network the EN...

Page 79: ...egisters 1 2 is shown below in Table 17 Table 18 Table 17 Register 1 Numerical Reading with Sign Decimal Point Bit Field Assignments Bit s Value Field 15 Sign of Reading 0 Positive 1 Negative 14 13 Fo...

Page 80: ...7 6 Alarm 2 Status 0 No Alarm 1 Unacknowledged Alarm 2 Acknowledged Alarm 3 Unused Code 5 4 Alarm 1 Status 0 No Alarm 1 Unacknowledged Alarm 2 Acknowledged Alarm 3 Unused Code 3 Overscale Status 0 No...

Page 81: ...egister 14 is the alarm 2 set point The decimal point location is the same as specified in Register 1 Registers 15 19 Registers 15 19 are the Gas Name ASCII String NULL Terminated Registers 20 22 Regi...

Page 82: ...n seconds Register 32 Register 32 is the alarm 2 OFF delay Integer values are in seconds Register 33 Register 33 is zero suppression Toxics and LEL 0 6 of full scale Oxygen 0 0 7 Oxygen The decimal po...

Page 83: ...libration Is Overscale 12 LEL Sensor Offset Is Too High 13 LEL Null Operation Failed 14 Operation Not Performed Register 39 Register 39 is the auto zero disable 0 AutoZero Enabled 1 AutoZero Disabled...

Page 84: ...M2A XL It is useful for remotely silencing alarms With the M2A XL in an alarm condition bit 0 can be used to silence it NOTE Register 40 in Function Code 03 the remote configuration register must be...

Page 85: ...140RK 05 LEL detector catalytic type CSA version 61 0140RKA CH4 ppm detector catalytic type UL version 61 0140RKA 05 CH4 ppm detector catalytic type CSA version 61 0190RK CH4 CH4 0 100 LEL 0 5 00 volu...

Page 86: ...membrane for 65 2302 SO2 10 detector 65 2039RK Plug in H2S sensor for 65 2428 01 detector 65 2049 01 CT 7 Series plug in sensor 0 15 0 ppm HCN with membrane for 65 2302 HCN 15 detector 65 2051 01 CT 7...

Page 87: ...10 CT 7 Series detector 0 10 0 ppm sulfur dioxide includes sensor 65 2428 H2S detector assembly 0 100 ppm CSA version includes plug in sensor 65 2428 01 H2S detector assembly CSA version for frequent...

Page 88: ...cylinder CO2 2 000 ppm in nitrogen 103 liter 81 0071RK 01 Calibration cylinder CO2 5 000 ppm in nitrogen 34 liter steel 81 0071RK 03 Calibration cylinder CO2 5 000 ppm in nitrogen 103 liter 81 0072RK...

Page 89: ...ob 0 25 LPM for 34 liter aluminum 58 liter 103 liter cylinders Used to calibrate NH3 ESM 01 M2A XL only 81 1103RK Calibration cup for 3 4 NPT IR detectors 81 1117RK Calibration cup for catalytic LEL p...

Page 90: ...01 plug in sensor 0 3 00 ppm chlorine ESM K01D CL2 10 ESM 01 plug in sensor 0 10 0 ppm chlorine NC 6205 01 Hydrogen specific LEL detector catalytic type UL version NC 6205 05 Hydrogen specific LEL de...

Page 91: ...Table 21 Control Button Quick Reference Chart Mode Entered or Function Performed Button Combination Adjustable or Viewable Parameters Alarm Reset Press and Release ENTER n a Show Information Screen P...

Page 92: ...strip If the PWR SIG terminal strip connections and one or more relays are used route the connections to the M2A XL in conduit Use shielded cable in the conduit for the PWR SIG connections and unshie...

Page 93: ...XL Figure 36 PLC and DCS Device Wiring Alarm 1 Alarm Device Fail Alarm Device Alarm Device Power Typical Alarm Wiring Shown 4 20 mA In S 24 VDC 24 VDC 24 VDC Power Supply 24 VDC Alarm 2 Alarm Device S...

Page 94: ...1 Increasing Register 3 Register 3 is the alarm 1 relay state 0 Normally De Energized 1 Normally Energized Register 4 Register 4 is the alarm 1 relay reset 0 Latching 1 Self Resetting Register 5 Regis...

Page 95: ...y Integer value is in seconds Register 13 Register 13 is the zero suppression Toxics and LEL 0 6 Full Scale Oxygen 0 0 7 Oxygen Value must be an integer Any decimals are omitted Register 14 Register 1...

Page 96: ...t the controller This register can be used to clear those flags Register 20 Register 20 is the AutoZero Disable 0 AutoZero Enabled 1 AutoZero Disabled Register 21 Register 21 is the Remote Configurati...

Reviews: