34 • Chapter 6: Advanced Configuration Menu
AirLink 7010 Gas Monitor Operator’s Manual
Relay Setup
1. Set Fault Relay: Press
ADD
or
SUB
(Yes/No—as indicated on the display screen) to setup Relay 4
as the Fault Relay. To leave the setting as it is, press
MENU
(Next).
NOTE:
With this feature enabled, if any Fault occurs (on any channel) the Fault Relay is engaged. In
addition, Relay 4 is removed from all setup options.
2. Failsafe: Press
ADD
or
SUB
(Yes/No—as indicated on the display screen) to setup Relay 1 as
failsafe (or not failsafe). To leave the setting as it is, press
MENU
(Next).
3. Repeat step 2 for Relays 2, 3, and 4.
4. Fault Terminal Failsafe: Press
ADD
or
SUB
(Yes/No—as indicated on the display screen) to setup
the Fault terminal as failsafe (or not failsafe). To leave the setting as it is, press
MENU
(Next).