16
•
Chapter 3: Installation & Startup
65-2646RKS-SW M2A Transmitter Operator’s Manual
Chapter 3: Installation & Startup
Overview
This chapter describes procedures to mount the M2A Transmitter in the monitoring environment
and wire it to input power and devices.
Mounting the M2A Transmitter
1. Select a mounting site that is representative of the monitoring environment. Consider the
following when you select the mounting site.
• Select a site where the junction box is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration procedures. The
site should be easily accessible.
• Select a site where the target gas is likely to be found first. For lighter gases, mount the
detector near the ceiling; for heavier gases, mount the detector near the floor.
2. Use #10
screws through the M2A junction box’s two mounting slots to secure the junction
box to a vertical surface. Figure 6 shows the outline and mounting dimensions. Mount the
M2A with the detector facing down as shown in Figure 6.
Figure 6: Outline & Mounting Dimensions
3/4 NPT
Conduit Port,
Plugged
3/4 NPT
Conduit Port
8.6 max
3.4 max
5.23
.47 (2X)
2.41
5.00
.30 (2X)
5.86
1.02
4.59