65-2641RK-03 M2A Transmitter Operator’s Manual
To discard the settings and review them again, press the DOWN/NO button. The display will ask
DO
OVER? YES/NO
. Press the UP/YES button and the display will indicate
Re-do Config
, then display the
target gas and the detection range for a few seconds before returning to Configuration Mode. Repeat steps 6
- 8 until the settings are as desired.
9. After the M2A completes its warm-up sequence, the display will indicate
CAL NEEDED
. Since the gas
type has been changed, a successful calibration must be performed before the M2A can enter normal
operation.
10. Press and release the UP/YES button to enter Calibration Mode. Normally, you must hold the UP/YES
button for 5 seconds to enter Calibration Mode, but since a calibration is required, only a momentary push is
needed to enter Calibration Mode after changing the gas type.
11. See “Calibration” on page 36 for calibration instructions.
NOTE:
When calibrating an M2A after changing the gas type, the M2A will not ask if you want to calibrate,
or whether you want to perform a fresh air adjustment, span adjustment or zero adjustment. Since a
complete calibration is required, the calibration sequence will proceed without asking if you want to
perform certain operations.