65-2641RK-03 M2A Transmitter Operator’s Manual

Chapter 4: Operation

Overview

This chapter describes the M2A in normal operation. This chapter also describes the M2A in alarm 1, alarm 2, 
and fail conditions and suggests responses to these conditions.

Normal Operation

Normal operation is defined as follows:

The start-up procedure is complete.

The M2A is not indicating an alarm 1, alarm 2, or fail condition.

The M2A is not in Calibration, Configuration, or Gas Type modes.

During normal operation, the M2A simultaneously displays the current gas reading, unit of measure, and target 
gas. 

Information Screen

The Information Screen displays the M2A’s operating voltage and firmware and hardware information. To 
display the Information Screen, do the following:

1. Press and hold the DOWN/NO button for 3 seconds. The Information Screen will appear.

2. Continue holding the DOWN/NO button to keep the Information Screen on the display. The top line 

indicates the operating voltage that is connected to the M2A. The second line indicates the firmware that is 
running, version 5.0 in this example, and the M2A’s hardware version, version 2A in this example. This 
information may be useful if you need to contact the factory with questions about the M2A.

3. Release the DOWN/NO button when you are done viewing the Information Screen. The display will return 

to the normal operation screen within a couple of seconds.

HYDROGEN

0 %LEL

24.2V         

   

v5.0L 2A

      

Summary of Contents for 65-2641RK-03

Page 1: ...RKI Instruments Inc www rkiinstruments com 65 2641RK 03 M2A Transmitter Operator s Manual Part Number 71 0400 Revision E Released 8 28 20...

Page 2: ...Periodic calibration and maintenance of the gas monitor is essential for proper operation and correct readings Please calibrate and maintain this instrument regularly Frequency of calibration depends...

Page 3: ...replacement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTAT...

Page 4: ...8 Internal Description 10 Chapter 3 Installation Startup 14 Overview 14 Mounting the M2A Transmitter 14 Wiring the M2A Transmitter 16 Start Up 20 Chapter 4 Operation 22 Overview 22 Normal Operation 2...

Page 5: ...n 36 Replacing the Hydrogen Detector 38 Chapter 8 RS 485 Modbus Output 40 Overview 40 Wiring the M2A in a Modbus System 40 Using the M2A in a 4 wire Modbus System 43 Modbus Mode 43 Supported Modbus Fu...

Page 6: ...s visible through the window in the cover front face and provides a 4 20 mA signal which indicates the target gas reading for use by a gas monitoring controller recording device or programmable contro...

Page 7: ...m 1 Alarm 2 10 LEL 50 LEL Construction housing Explosion proof Junction Box NEMA 4X Area Classification Explosion proof for Class I Groups B C and D Sampling Method Diffusion Input Power 10 30 VDC Con...

Page 8: ...the detector needs to be installed at an inaccessible location The detector junction box can be installed at the inaccessible location and the M2A junction box can be installed in a more readily acce...

Page 9: ...ed to one side of this terminal strip The other side of the terminal strip is for user supplied wiring to the detector terminal strip located in the M2A junction box This wiring should go through the...

Page 10: ...ange and an RS 485 Modbus output signal The 4 20 mA signal may be used by a recording device gas monitor controller or programmable controller The Modbus output may be used to connect the M2A to a Mod...

Page 11: ...is factory wired to the M2A See Wiring the M2A Transmitter on page 16 for all wiring procedures related to M2A Modbus Terminal Strip The Modbus terminal strip is a three position plug in style termina...

Page 12: ...inal PCB by lining up its three spacing standoffs with the banana jacks in the terminal PCB mounting standoffs and pushing it onto the banana jacks The jacks retain the control PCB Figure 4 Control PC...

Page 13: ...4 Fail LED The fail LED turns on when the M2A is experiencing a fail condition A fail condition can be caused by a detector failure or low detector signal Alarm 1 LED The alarm 1 LED is on when the M...

Page 14: ...The site should be easily accessible For the detector junction box select a site where the target gas is likely to be found first For lighter gases mount the detector near the ceiling for heavier gas...

Page 15: ...h I D flexible polyurethane tubing to the fitting at the bottom of the calibration adapter and route it to an accessible area that is close to the M2A junction box See the Chapter 9 Parts List on page...

Page 16: ...h the top conduit hub of the detector junction box To make wiring more convenient use wire colors that correspond to the detector wire colors red white green and black 9 Connect the wires to the termi...

Page 17: ...ou will connect the opposite end of the cable s drain wire to the M2A junction box s chassis earth ground Figure 7 Wiring the Detector to the M2A 14 Reinstall the detector terminal strip into its sock...

Page 18: ...x B PLC and DCS Device Wiring on page 52 then continue with step 8 Use the following recommendations to determine how to wire the M2A If Modbus connections will not be used and only the PWR SIG connec...

Page 19: ...junction box 5 Make controller device and relay connections as appropriate If shielded cable is used for the PWR SIG connections connect the cable shield s drain wire to an available chassis ground at...

Page 20: ...esence of hydrogen in the monitoring environment use the calibration kit and the zero air calibration cylinder to introduce fresh air to the detector and verify an accurate fresh air setting See the C...

Page 21: ...o enter Calibration Mode Release the button when the following screen appears 2 Press and release the UP YES button to continue The display will indicate the target gas and CAL Mode for a few seconds...

Page 22: ...ion Screen displays the M2A s operating voltage and firmware and hardware information To display the Information Screen do the following 1 Press and hold the DOWN NO button for 3 seconds The Informati...

Page 23: ...ration If the M2A s input power decreases below 18 5 volts so that the M2A is in a low power alarm the signal output is fixed below 2 4 mA until the low power alarm is cleared If the M2A goes into a f...

Page 24: ...reset the alarm 1 circuit Resetting the alarm 1 circuit turns off the A1 LED resets the OLED display and de energizes the alarm 1 relay NOTE If the ENTER button is pressed while the M2A is in an alarm...

Page 25: ...il Condition Indications The M2A indicates a fail condition for any of the following The detector wiring is disconnected or incorrectly connected The display reading is 10 of full scale or lower When...

Page 26: ...equence Responding to a Low Power Condition 1 Determine and correct the cause of the low power condition 2 When the input power increases above 10 0 volts the M2A will begin its warm up sequence 3 Ver...

Page 27: ...tons when the following screen appears 2 If you want to exit Configuration Mode press and release the DOWN NO button and the M2A will return to normal operation If you want to continue in Configuratio...

Page 28: ...at which the M2A initiates an alarm 2 condition ALARM 2 activation Increase Indicates if the alarm 2 circuit is activated by gas readings increasing Increase or decreasing Decrease to the ALARM 1 Lev...

Page 29: ...ero suppression is 2 0 LEL the M2A will display a reading of 0 LEL for gas readings from 2 LEL to 2 LEL It is settable from 0 to 6 of the detection range FILTER 5 secs The filter feature helps smooth...

Page 30: ...lly returns to normal operation NOTE If the M2A enters normal operation because of a program time out it enters a warm up period just as it does when it is first turned on Selecting the Gas Type 1 Whi...

Page 31: ...gs in Configuration Mode can be verified or changed 6 While in Configuration Mode press and release the ENTER button to accept the displayed parameter setting and move to the next one Use the UP YES a...

Page 32: ...ration must be performed before the M2A can enter normal operation 10 Press and release the UP YES button to enter Calibration Mode Normally you must hold the UP YES button for 5 seconds to enter Cali...

Page 33: ...s probable causes and recommended action for problems you may encounter with the M2A NOTE This troubleshooting guide describes M2A problems only If the M2A is connected to a controller see the control...

Page 34: ...lded See Wiring the M2A Transmitter on page 16 2 Verify that the detector wiring is correct and secure 3 Increase the filter setting in Configuration Mode 4 Increase the zero suppression setting in Co...

Page 35: ...er for this operation 4 Use the flexible tubing coming from the calibration adapter to connect the regulator to the calibration adapter 5 Turn the regulator s on off knob counterclockwise to open the...

Page 36: ...zero air cylinder and a fixed flow regulator with an on off knob NOTE The detector must be calibrated with a gas concentration between 10 and 100 of the channel s full scale value ie between 10 LEL a...

Page 37: ...e fresh air reading press and release the UP YES button ENTER will alternate with FreshAir on the top display line and the current gas reading will be on the bottom display line To skip adjusting the...

Page 38: ...d alarms During this 1 minute period the signal output will remain fixed at 3 5 mA and the relays will remain in their non alarm state to avoid unwanted alarms while the calibration gas clears from th...

Page 39: ...ator s Manual 39 10 Turn on or plug in power to the M2A NOTE Allow the replacement detector to warm up for 15 minutes before you continue with the next step 11 Calibrate the replacement detector as de...

Page 40: ...12 below illustrate typical M2A wiring configurations If more than 128 M2As need to be connected together RS 485 repeater s should be used such that no more than 128 M2As reside on any given network...

Page 41: ...should only be done if wiring for a system that is being replaced is already installed and it is not practical to run another wire See Figure 10 below for this wiring configuration In this configurat...

Page 42: ...n an M2A that is at the end of a Modbus line Any M2A in a Modbus system that is not at the end of a line must have the termination jumper removed see Figure 11 Figure 12 below Figure 11 Multiple M2As...

Page 43: ...ically returns to normal operation NOTE If the M2A returns to normal operation because of a time out it enters a warm up period just as it does when it is first turned on 1 While in normal operation s...

Page 44: ...ormal operation NOTE All M2As on a Modbus network must be configured with the same baud rate and parity and each M2A must have a unique slave ID For an M2A to participate on a network the ENABLED DISA...

Page 45: ...ading with Sign Decimal Point Bit Field Assignments Bit s Value Field 15 Sign of Reading 0 Positive 1 Negative 14 13 Format of Reading 0 XXX no decimal point 1 XX X 2 X XX 3 XXX 12 0 Numerical value o...

Page 46: ...1 Register 14 Register 14 is the alarm 2 set point The decimal point location is the same as specified in Register 1 8 Fail Status 0 Fail Not Asserted 1 Fail Asserted 7 6 Alarm 2 Status 0 No Alarm 1 U...

Page 47: ...m 1 relay reset 0 Latching 1 Self Resetting Register 26 Register 26 is the alarm 1 ON delay Integer values are in seconds Register 27 Register 27 is the alarm 1 OFF delay Integer values are in seconds...

Page 48: ...0 and the 1st 0 Register 37 Register 37 is the calibration year Register 38 Register 38 is the calibration outcome Upper Gas Operation Lower Air Operation Calibration Outcome Codes 1 Sensor Missing 2...

Page 49: ...ction Code 16 see Appendix C Function Code 16 Registers on page 54 Register 16 Register 16 performs the same function as the ENTER button on the M2A It is useful for remotely silencing alarms With the...

Page 50: ...ansmitter Operator s Manual this document 81 0002RK 01 Calibration cylinder 50 LEL hydrogen in air 34 liter steel 81 0002RK 03 Calibration cylinder 50 LEL hydrogen in air 103 liter steel 81 0076RK 01...

Page 51: ...utton Quick Reference Chart Mode Entered or Function Performed Button Combination Adjustable or Viewable Parameters Alarm Reset Press and Release ENTER n a Show Information Screen Press and Hold DOWN...

Page 52: ...PWR SIG terminal strip connections and one or more relays are used route the connections to the M2A in conduit Use shielded cable in the conduit for the PWR SIG connections and unshielded cable or in...

Page 53: ...LC and DCS Device Wiring Alarm Device Power Fail Alarm Device Alarm 1 Alarm Device 24 VDC 24 VDC Power Supply 24 VDC Typical Alarm Wiring Shown 24 VDC 4 20 mA In S Alarm 2 Alarm Device C NC NO ALARM 1...

Page 54: ...Normally De Energized 1 Normally Energized Register 4 Register 4 is the alarm 1 relay reset 0 Latching 1 Self Resetting Register 5 Register 5 is the alarm 1 ON delay Integer value is in seconds Regist...

Page 55: ...5 second increments Register 15 Register 15 is the calibration timeout Value is in minutes 5 10 15 20 25 or 30 Register 16 Register 16 is explained in Supported Modbus Functions in the M2A manual Regi...

Page 56: ...Transmitter Operator s Manual Register 20 Register 20 is the AutoZero Disable 0 AutoZero Enabled 1 AutoZero Disabled Register 21 Register 21 is the Remote Configuration Register 0 No Remote Configura...