65-2396RK CO
2
Transmitter • 5
Overview
This manual describes the 65-2396RK CO
2
transmitter. This manual also describes how to install, start
up, configure, maintain, and calibrate the transmitter when it is used with a gas monitoring controller.
A parts list at the end of this manual lists replacement parts and accessories for the CO
2
transmitter.
Specifications
Table 1 lists specifications for the CO
2
transmitter.
WARNING: When using the 65-2396RK, you must follow the instructions and warnings in this
manual to assure proper and safe operation of the 65-2396RK and to minimize the
risk of personal injury. Be sure to maintain and periodically calibrate the 65-2396RK
as described in this manual.
Table 1:Specifications
Target Gas
Carbon Dioxide (CO
2
)
Area Classification
Explosionproof for Class I, Groups B, C, and D
Sampling Method
Diffusion
Signal Output
4 to 20 mA
Detection Range
65-2396RK-01: 0-9,000 ppm
65-2396RK-02: 0-5,000 ppm
65-2396RK-03: 0-5% Volume
65-2396RK-04: 0-20% Volume
65-2396RK-05: 0-50% Volume
65-2396RK-10: 0-100% Volume
Response Time
90% in 45 seconds
Operating Temperature
-4°F to 122°F (-20°C to 50°C)
Accuracy
± 5% of reading or ± 2% of full scale (whichever is greater)