![RKI Instruments 65-2380 Operator'S Manual Download Page 14](http://html1.mh-extra.com/html/rki-instruments/65-2380/65-2380_operators-manual_1466807014.webp)
14
•
Maintenance
6. Screw the regulator into the zero air calibration cylinder.
7. Use the calibration kit sample tubing to connect the regulator to the calibration cup.
8. Turn the regulator’s on/off knob counterclockwise to open it. Gas will begin to flow.
9. Allow the gas to flow for one minute.
10. Verify a voltmeter reading of 100 mV (±2 mV).
11. If necessary, use a small flat-blade screwdriver to adjust the zero pot until the voltmeter
reading is 100 mV (±2 mV).
12. Turn the regulator’s on/off knob clockwise to close it.
13. Unscrew the calibration cup from the detector.
14. Unscrew the regulator from the zero air calibration cylinder. For convenience, leave the
sample tubing connected to the regulator and the calibration cup.
15. Store the components of the calibration kit in a safe and convenient place.
16. Remove the voltmeter leads from the test points.
17. Secure the junction box cover to the junction box.
Maintenance
This section describes maintenance procedures. It includes preventive maintenance,
troubleshooting, and component replacement procedures.
Preventive Maintenance
This section describes a preventive maintenance schedule to ensure the optimum performance of
the combustible gas transmitter. It includes daily and biannual procedures.
Daily
Verify a display reading of 0% LEL at the controller. Investigate significant changes in the display
reading.
Biannually
Calibrate the combustible gas transmitter as described in “Calibration” on page 18 of this manual.