WARNING: Do not use this product in a manner not specified in this instruction manual.
7DEOHOLVWVVSHFLILFDWLRQ
6WUDQVPLWWHU
127(
7KHIROORZLQJV\PERORQWKHGHWHFWRUODEHOLVDFDXWLRQWRWKHXVHUWRUHIHUWRWKLV
GRFXPHQWDWLRQIRULQVWDOODWLRQDQGRSHUDWLRQLQVWUXFWLRQV
WARNING: When using the 65-2331RK, you must follow the instructions and warnings in
this manual to assure proper and safe operation of the 65-2331RK and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 65-2331RK as described in this manual.
7DEOH6SHFLILFDWLRQV
Target Gas
Hydrogen sulfide (H
2
S)
Area Classification
Explosion-proof for Class I, Groups B, C, and D
Temperature Code
T6
Installation Category
Installation Category 1. Signal level, special equipment or
parts of equipment, telecommunication, electronic, etc., with
smaller transient overvoltages than Installation Category
(Overvoltage Category) II (ref. IEC 664).
Input Voltage
11 VDC - 30 VDC
Sampling Method
Diffusion
Signal Output
4 to 20 mA
Detection Range
0 to 100 PPM (parts per million)
Accuracy
± 5% of reading or ± 2 ppm H
2
S (whichever is greater)
H
2
S Detector Signal
Output
0.3 mA at 0 ppm H
2
S nominal
2.5 mA at 100 ppm H
2
S nominal
Response Time
90% in 30 seconds
Operating Temperature
-40°F to 104°F (-40°C to 40°C)