background image

IMS01N12-E2 

4. COMMUNICATION SETTING 

Set communication setting before mounting and wiring of SRX. 

 
 

Do not separate the module mainframe from the terminal 
base with the power turned on. If so, instrument failure 
may result. 

 

 

Setting at using PLC communication   

 Address setting switch 1 (front) [Refer to P. 4]

 

Set an address of module.

 

 Address setting switch 2 (left side) [Refer to P. 4]

 

Set the unit address for PLC communication.

 

 PLC communication setting switch (left side) [Refer to P. 5]

 

Set the communication speed, data bit configuration, and protocol 
for PLC communication. Set the same value as communication 
settings of PLC. 
In addition, select the communication port of modular connector.

 

 Host communication setting switch 1 (right side) [Refer to P. 6]

 

Set the communication speed, data bit configuration, and protocol 
for host communication using 

host communication terminals

. Set 

the same value as communication settings of host computer.

 

 

 

 

Setting at using host communication 1 

 Address setting switch 1 (front) [Refer to P. 4]

 

Set an address of module.

 

 Address setting switch 2 (left side) [Refer to P. 4]

 

Set the unit address for host communication 1.

 

 

PLC communication setting switch (left side) [Refer to P. 5]

 

S

elect the communication port of modular connector.

 

 Host communication setting switch 2 (left side) [Refer to P. 5]

 

Set the communication speed, data bit configuration, and protocol 
for host communication 1. Set the same value as communication 
settings of host computer. 

 Host communication setting switch 1 (right side) [Refer to P. 6]

 

Set the communication speed, data bit configuration, and protocol 
for host communication using 

host communication terminals

. Set 

the same value as communication settings of host computer.

 

 

 

 

Setting at using host communication 2 

 Address setting switch 1 (front) [Refer to P. 4]

 

Set an address of module.

 

 Address setting switch 2 (left side) [Refer to P. 4]

 

Set the unit address for host communication 2.

 

 PLC communication setting switch (left side) [Refer to P. 5]

 

Set the communication speed, data bit configuration, and protocol 
for host communication 2. Set the same value as communication 
settings of host computer. 
In addition, select the communication port of modular connector.

 

 Host communication setting switch 1 (right side) [Refer to P. 6]

 

Set the communication speed, data bit configuration, and protocol 
for host communication using 

host communication terminals

. Set 

the same value as communication settings of host computer.

 

 

 

 

Host communication 
setting switch 1 

PLC communication setting switch 

Host communication setting switch 2 

Address setting switch 2 

Address setting switch 1

Left side view 

Right side view

Front view 

Module mainframe 

Terminal base 

FAIL/RUN

RX/TX 

EVENT1 

EVENT2 

EVENT3 

EVENT4 

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

 

4.1 Address Setting 

Set an address. For this setting, use a small slotted screwdriver. 

 

To avoid problems or malfunction, do not duplicate 
an address on the same communication line.

 

 

 

Module address setting 

When using two or more modules, set the desired address to 
each module. 
(Common to PLC communication and host communication) 

 

High-order digit setting
(set value 

 10) 

Setting range: 0 to 95 
(Factory set value: 0) 

Low-order digit setting 
(set value 

 1) 

Address setting switch 1 (for module address) 

FAIL/RUN

RX/TX 

EVENT1

EVENT2

EVENT3

EVENT4

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

 

 

 

Do not set address 96 to 99.   
Otherwise, malfunction may result.

 

 

For Modbus, the value obtained by adding “1” to 
the set address corresponds to the address used 
for the actual program. 

 

Set the module address such that it is different to 
the other addresses on the same line. Otherwise, 
problems or malfunction may result. 

 

 

Unit address setting 

When two or more X-TIO-R modules are multi-drop connected, 
set an address to each X-TIO-R module. This becomes the unit 
address of the SRX unit.   
(Common to PLC communication/host communication) 

 

 

Left side view

 

Setting range:  

0 to 15 [0 to F: hexadecimal]
(Factory set value: 0) 

9

8

7

C

B

A

6

5

4

3

2

1

0

F

E

D

Address setting switch 2 

(for unit address) 

 

 

 

PLC communication 

Up to four X-TIO-R modules can be connected to a PLC 
communication port. Therefore the unit address uses the four 
X-TIO-R modules as a group. Use consecutive numbers in any 
one of four groups in the following table as unit address.

 

 

Group

Address setting 

switch 2 

 

Group 

Address setting 

switch 2 

Group 1

 Group 

 

 

 

 

 

 

Group 2

 Group 

 

 

 

 

 

 

 

Always set the unit address of each group including 
0, 4, 8 or C. 0, 4, 8 or C becomes the master for 
communication transfer. 

CAUTION 

Summary of Contents for X-TIO-R

Page 1: ...y operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power must be turned off before repairing work for input break and output failure in...

Page 2: ...Extension type X TIO B Digital input DI module X DI A X DI B Digital output DO module X DO A X DO B Up to 29 modules Temperature control module for PLC communication X TIO R For communication port assignments refer to the 4 2 Protocol Selections and Communication Speed Setting P 5 All data are set by communication For details refer to the Module Type Controller SRX PLC Host Communication Instructi...

Page 3: ...l cover Indication lamps 2 Modular connector COM PORT1 Modular connector COM PORT2 Modular connector COM PORT3 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 PLC host communication side Temperature control side 5 4 3 2 1 0 9 8 7 6 5 5 4 3 2 1 0 9 8 7 6 5 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 Indication lamps 1 FAIL RUN for temperature control When normally A green lamp turns on RUN When abnormall...

Page 4: ...ctor Host communication setting switch 1 right side Refer to P 6 Set the communication speed data bit configuration and protocol for host communication using host communication terminals Set the same value as communication settings of host computer Host communication setting switch 1 PLC communication setting switch Host communication setting switch 2 Address setting switch 2 Address setting switc...

Page 5: ...tory set value Host communication 2 RKC communication 8 Communication port assignment OFF COM PORT1 PLC communication host communication 2 RS 232C RS 422A COM PORT2 COM PORT3 Host communication 1 RS 422A ON COM PORT1 Host communication 1 RS 232C RS 422A COM PORT2 COM PORT3 PLC communication host communication 2 RS 422A Factory set value COM PORT1 Host communication 1 RS 232C RS 422A COM PORT2 COM ...

Page 6: ...lection OFF RKC communication ON Modbus Factory set value RKC communication 8 Internal data bus termination resistor setting OFF Termination resistor OFF ON Termination resistor ON Factory set value Termination resistor OFF Switch No 7 must be always OFF Do not set to ON When connecting two or more modules TIO module Extension type etc to the X TIO R module match all of their communication speed d...

Page 7: ... the immunity to withstand noise mount this instrument as far away as possible from high voltage equipment power lines and rotating machinery High voltage equipment Do not mount within the same panel Power lines Separate at least 200 mm Rotating machinery Separate as far as possible Ensure at least 50 mm space on top and bottom of the control unit for maintenance and environmental reasons 5 In cas...

Page 8: ...tab insertion slot 6 WIRING 6 1 Wiring Cautions For thermocouple input use the appropriate compensation wire For RTD input use low resistance lead wire with no difference in resistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment Signal connected to Voltage input and Current input...

Page 9: ...g input only for Voltage Current input In this case control output 2 and CT input 2 become unused 6 3 Pin Layout of Connector Modular connector Modular connector 6 1 COM PORT1 COM PORT2 COM PORT3 Modular connector COM PORT1 Connector for PLC or Host computer connection Based on RS 422A RS 232C Specify when ordering Modular connector COM PORT2 Connector for PLC or Host computer connection Based on ...

Page 10: ...nction Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm HBA function Number of HBA 2 points Setting range 0 0 to 100 0 A 0 0 A OFF Additional function Number of event delay times 1 to 255 times Control loop break alarm LBA function Number of LBA 2 points LBA time 1 to 7200 seconds ...

Reviews: