background image

IMS01N12-E2 

 

3

2. PRODUCT CHECK 

Before using this product, check each of the following: 

 Model code 

  Check that all of the accessories delivered are complete. 

 Check that there are no scratch or breakage in external 

appearance (case, front panel, or terminal, etc). 

X-TIO-R- 

 

 - 

 

 

 

 - 

 / Y 

(1) (2) (3)  (4) (5) (6) 

(7) (8) (9) 

 

(1) Type 

R:  Module for PLC communication 

(2) Input channel 1,  (3) Input channel 2 

K:  Thermocouple K 

D:  RTD Pt100 

J:  Thermocouple J 

P:  RTD JPt100 

T:  Thermocouple T 

1:  0 to 10 mV DC 

S:  Thermocouple S 

2:  0 to 100 mV DC 

R:  Thermocouple R 

3:  0 to 1 V DC 

A: Thermocouple PL

 

4:  0 to 5 V DC 

N:  Thermocouple N 

5:  0 to 10 V DC 

E:  Thermocouple E 

6:  1 to 5 V DC 

W:  Thermocouple W5Re/W26Re  7:  0 to 20 mA DC 
B:  Thermocouple B 

8:  4 to 20 mA DC 

(4) Control output 1,  (5) Control output 2 

M:  Relay contact output 
V:  Voltage pulse output 0/12 V DC 
4:  0 to 5 V DC 
5:  0 to 10 V DC 
6:  1 to 5 V DC 
7:  0 to 20 mA DC 
8:  4 to 20 mA DC 

(6) CT1 input,  (7) CT2 input 

N: None 
P: CTL-6-P-N 
S: CTL-12-S56-10L-N 

(8) Communication function (COM. PORT1) 

*

 

1: RS-232C 
4: RS-422A 

*

 Host communication terminals is RS-485 (Fixed),   

COM. PORT2/COM. PORT3 is RS-422A (Fixed). 

(9) Version symbol 

No code: For Japanese domestic market   
/Y: 

For International market 

 

Heater break alarm (HBA) function cannot be used 
when control output is Voltage/Current output.

 

 

 
 
 
 
 
 
 

If any of the products are missing, damaged, or if your 
manual is incomplete, please contact RKC sales office 
or the agent.

 

 

3. PARTS DESCRIPTION 

 

Terminal cover

Indication lamps 1

Address setting
switch 1 

Terminal cover

Indication lamps 2

Modular connector

COM. PORT1 

Modular connector 

COM. PORT2 

Modular connector 

COM. PORT3 

FAIL/RUN 

RX/TX 

EVENT1 

EVENT2 

EVENT3 

EVENT4 

PLC/host communication side Temperature control side 

5

4

3

2

1

0

9

8

7

6

5

5

4

3

2

1

0

9

8

7

6

5

 

 

FAIL/RUN 
RX/TX 
EVENT1 
EVENT2 
EVENT3 
EVENT4 

 

 
 
 
[Indication lamps 1] 

 FAIL/RUN (for temperature control) 

When normally: 

A green lamp turns on (RUN) 

When abnormally: 

A red lamp turns on (FAIL) 

During self-diagnostic error:  A green lamp flashes   

 RX/TX (for internal communication) 

During data send and receive:  A green lamp turns on 

 EVENT 1 to 4 

Display various states by setting. 

Display contents: 
Event 1 state, Event 2 state, Comprehensive event state, 
Output state, Control state, Execution segment state, Time 
signal state 

[Indication lamps 2] 

 FAIL (for PLC/host communication) 

When normally: 

A red lamp turns off 

When abnormally: 

A red lamp turns on 

Communication environment setting mode by the switch: 
 

A red lamp flashes 

 RUN (for PLC/host communication) 

When normally: 

A green lamp turns on 

When abnormally: 

A green lamp turns off 

Memory backup error: 

A green lamp flashes slowly 

Module configuration error:  A green lamp flashes slowly 
PLC communication error:  A green lamp flashes slowly 
Data collection just after the power is turned on: 
 

A green lamp flashes rapidly 

 COM. PORT1 

During data send and receive:  A yellow lamp turns on 

 COM. PORT2/COM. PORT3 

During data send and receive:  A yellow lamp turns on 

 
 

 

Accessories

 

End Plate ................................................................... 2 
Joint connector cover ................................................. 2 
X-TIO-R Instruction Manual (IMS01N12-E2) .............  1 

 

Indication
lamp 2 

Indication
lamp 1 

Temperature control side

PLC/host communication side 

FAIL
RUN
COM. PROT1
COM. PROT2/COM. PROT3

*

 

Summary of Contents for X-TIO-R

Page 1: ...y operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power must be turned off before repairing work for input break and output failure in...

Page 2: ...Extension type X TIO B Digital input DI module X DI A X DI B Digital output DO module X DO A X DO B Up to 29 modules Temperature control module for PLC communication X TIO R For communication port assignments refer to the 4 2 Protocol Selections and Communication Speed Setting P 5 All data are set by communication For details refer to the Module Type Controller SRX PLC Host Communication Instructi...

Page 3: ...l cover Indication lamps 2 Modular connector COM PORT1 Modular connector COM PORT2 Modular connector COM PORT3 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 PLC host communication side Temperature control side 5 4 3 2 1 0 9 8 7 6 5 5 4 3 2 1 0 9 8 7 6 5 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 Indication lamps 1 FAIL RUN for temperature control When normally A green lamp turns on RUN When abnormall...

Page 4: ...ctor Host communication setting switch 1 right side Refer to P 6 Set the communication speed data bit configuration and protocol for host communication using host communication terminals Set the same value as communication settings of host computer Host communication setting switch 1 PLC communication setting switch Host communication setting switch 2 Address setting switch 2 Address setting switc...

Page 5: ...tory set value Host communication 2 RKC communication 8 Communication port assignment OFF COM PORT1 PLC communication host communication 2 RS 232C RS 422A COM PORT2 COM PORT3 Host communication 1 RS 422A ON COM PORT1 Host communication 1 RS 232C RS 422A COM PORT2 COM PORT3 PLC communication host communication 2 RS 422A Factory set value COM PORT1 Host communication 1 RS 232C RS 422A COM PORT2 COM ...

Page 6: ...lection OFF RKC communication ON Modbus Factory set value RKC communication 8 Internal data bus termination resistor setting OFF Termination resistor OFF ON Termination resistor ON Factory set value Termination resistor OFF Switch No 7 must be always OFF Do not set to ON When connecting two or more modules TIO module Extension type etc to the X TIO R module match all of their communication speed d...

Page 7: ... the immunity to withstand noise mount this instrument as far away as possible from high voltage equipment power lines and rotating machinery High voltage equipment Do not mount within the same panel Power lines Separate at least 200 mm Rotating machinery Separate as far as possible Ensure at least 50 mm space on top and bottom of the control unit for maintenance and environmental reasons 5 In cas...

Page 8: ...tab insertion slot 6 WIRING 6 1 Wiring Cautions For thermocouple input use the appropriate compensation wire For RTD input use low resistance lead wire with no difference in resistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment Signal connected to Voltage input and Current input...

Page 9: ...g input only for Voltage Current input In this case control output 2 and CT input 2 become unused 6 3 Pin Layout of Connector Modular connector Modular connector 6 1 COM PORT1 COM PORT2 COM PORT3 Modular connector COM PORT1 Connector for PLC or Host computer connection Based on RS 422A RS 232C Specify when ordering Modular connector COM PORT2 Connector for PLC or Host computer connection Based on ...

Page 10: ...nction Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm HBA function Number of HBA 2 points Setting range 0 0 to 100 0 A 0 0 A OFF Additional function Number of event delay times 1 to 255 times Control loop break alarm LBA function Number of LBA 2 points LBA time 1 to 7200 seconds ...