5.5 Jointing Each Module 

Up to 31 SRXs consisting of the each modules can be jointed 
together. Joint these modules according to the following 
procedure. 

 

 

Jointing procedure 

1. 

Mount the modules on the DIN rail and then joint these 
modules together with the joint connector while sliding the 
relevant module. 

2. 

Lift each of the joint tabs located at the top and bottom of the 
module and then insert it in the slot of the adjacent module to 
fix these two modules. 

 

For panel mounting, first joint each module and then 
mount it on the panel.

 

 

 

Joint tab 

Joint connector

When viewed 
from top 

There is one joint tab at each 
of the top and bottom of on 
module. Therefore, fix two 
adjacent modules with these 
two joint tabs. 

Joint tab 
insertion slot

 

 
 

6. WIRING 

 
 
 
 
 
 
 

 

6.1 Wiring Cautions 

 

For thermocouple input, use the appropriate compensation 
wire.

 

 

For RTD input, use low resistance lead wire with no 
difference in resistance between the three lead wires.

 

 

To avoid noise induction, keep input signal wire away from 
instrument power line, load lines and power lines of other 
electric equipment.

 

 

6.2 Terminal Configuration 

 

CT1

CT input 

Control output 1 

Control output 2

NO 

OUT1 

OUT1

+

5

2

3

6

7

Thermocouple

 

TC1

+

 

Input channel 1

Voltage/

current 

IN1

+

RTD

RTD1

B

B

A

NO

OUT2

OUT2 

+

 

 

4

1

10

13

10

14

13

13

10

Thermocouple

TC2 

+

 

Voltage/ 

current 

IN2 

+

 

 

RTD

12

8

12

12

RTD2

B

B

A

9

Input channel 2

3

7

14 13  12 

11 10  9 

CT2

Voltage pulse/

Current/ 

Voltage 

Relay contact 

Voltage pulse/ 

Current/ 

Voltage 

Relay contact

Upper-side terminal

Lower-side terminal

 

 

 

• 

Terminal No. 11 is not used.

 

• 

Input channel 2 can be used as remote setting input 
(only for voltage/current input).   
In this case, control output 2 and CT input 2 become 
unused.

 

• 

Use the solderless terminal appropriate to the screw 
size (M3)

.

 

 
 
 
 
 
 
 

7. SPECIFICATIONS 

 

Inputs 

Number of inputs: 

2 points (Isolated between each channel) 

Input type: 

 Thermocouple 

K, J, T, S, R, E, B, N (JIS-C1602-1995) 

  

PLII 

(NBS) 

  

W5Re/W26Re 

(ASTM-E988-96) 

 RTD: 

Pt100 (JIS-C1604-1997) 

   

JPt100 (JIS-C1604-1989, Pt100 of   

  

 

JIS-C1604-1981) 

 Voltage (low): 

0 to 10 mV, 0 to 100 mV, 0 to 1 V 

 Voltage (high): 

0 to 5 V, 0 to 10 V, 1 to 5 V 

 Current: 

0 to 20 mA, 4 to 20 mA 

   

(Input impedance: 250 

Sampling cycle: 

25 ms 

PV bias: 

Input span to 

+

Input span 

CT input: 

2 points 
 

0.0 to 30.0 A (CTL-6P-N) or 

 

0.0 to 100.0 A (CTL-12-S56-10L-N) 

 
 

 

 

 

 

To prevent electric shock or instrument failure, do 
not turn on the power until all the wiring is 
completed. 

!

 

WARNING 

5.9 mm or less

3.2 mm or more

Recommended tightening 
torque:

 0.4 N

m (4 kgf

cm) 