1. OUTLINE
One temperature control (TIO) module [extension type] enables
temperature control corresponding to two channels.
As the temperature control (TIO) module [extension type] is not
provided with terminals for power supply and host
communication, it is always used together with the module
(temperature control module [basic type] X-TIO-A, etc.) with
terminals for power supply and host communication.
The temperature control (TIO) module [extension type] can be
connected with the temperature control (TIO) module [basic
type], the temperature control (TIO) module for PLC
communication, the digital input (DI) module and the digital
output (DO) module.
All data are set by communication. For details, see the
Module Type Controller SRX Communication
Instruction Manual (IMS01N01-E )
.
Host computer
RS-485
Temperature
control module
[basic type]
X-TIO-A
Temperature
control module
[extension type]
X-TIO-B
Digital input
module
X-DI-A
Digital output
module
X-DO-A
Control
output
Digital
input
Digital
output
Measured
input
Control
output
Measured
input
Digital
input
Digital
output
SRX configuration example
2. PRODUCT CHECK
Before using this product, check each of the following:
•
Model code
•
Check that all of the accessories delivered are complete.
•
Check that there are no scratch or breakage in external
appearance (case, front panel, or terminal, etc).
X-TIO-B- -
/ Y
(1) (2) (3) (4) (5) (6) (7)
(1) Type
B: Extension type (14 terminals)
(2) Input channel 1, (3) Input channel 2
K: TC K
J: TC J
T: TC T
S: TC S
R: TC R
A: TC PL
Ⅱ
N: TC N
E: TC E
W: TC W5Re/W26Re
B: TC B
D: RTD Pt100
P: RTD JPt100
1: 0 to 10 mV DC
2: 0 to 100 mV DC
3: 0 to 1 V DC
4: 0 to 5 V DC
5: 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(4) Control output 1, (5) Control output 2
M: Relay contact output
V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC
5 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(6) CT1 input, (7) CT2 input
N: None
P: CTL-6-P-N
S: CTL-12-S56-10L-N
3. PARTS DESCRIPTION
Terminal cover
Indication lamps
Address setting
switch
Terminal cover
Joint connector
(Right-side)
Joint connector
(Left-side)
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
[Indication lamps]
FAIL/RUN
When normally:
A green lamp turns on (RUN)
When abnormally: A red lamp turns on (FAIL)
RX/TX
During data send and receive: A green lamp turns on
EVENT 1 to 4
Display various states by setting.
During ON state: A green lamp turns on
Display contents
Event 1 state, Event 2 state, Comprehensive event state,
Output state, Control state, Executing segment state,
Time signal state
4. COMMUNICATION SETTING
Set communication setting before mounting and wiring of SRX.
4.1 Module Address Setting
Set an address of module. For this setting, use a small blade
screwdriver.
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
High-order digit
setting
(Set value
×
10)
Setting range: 0 to 99
(Factory set value: 00)
Low-order digit
setting
(Set value
×
1)
Address setting switch
•
For Modbus, the value obtained by adding “1” to
the set address corresponds to the address used
for the actual program.
•
Set the module address such that it is different to
the other addresses on the same line. Otherwise,
problems or malfunction may result.
Accessories
Instruction Manual (IMS01N03-E3) ........................... 1
*