1. OUTLINE 

One temperature control (TIO) module [extension type] enables 
temperature control corresponding to two channels.

 

As the temperature control (TIO) module [extension type] is not 
provided with terminals for power supply and host 
communication, it is always used together with the module 
(temperature control module [basic type] X-TIO-A, etc.) with 
terminals for power supply and host communication. 
The temperature control (TIO) module [extension type] can be 
connected with the temperature control (TIO) module [basic 
type], the temperature control (TIO) module for PLC 
communication, the digital input (DI) module and the digital 
output (DO) module.

 

 

All data are set by communication. For details, see the 

Module Type Controller SRX Communication 
Instruction Manual (IMS01N01-E )

.

 

 

 

Host computer 

RS-485 

Temperature 

control module 

[basic type] 

X-TIO-A 

Temperature 

control module 

[extension type] 

X-TIO-B 

Digital input

module 

X-DI-A 

Digital output

module 

X-DO-A 

Control 

output 

Digital 

input 

Digital 

output 

Measured 

input 

Control 

output 

Measured 

input 

Digital 

input 

Digital 

output 

 

SRX configuration example 

 

 

2. PRODUCT CHECK 

Before using this product, check each of the following: 

• 

Model code 

• 

Check that all of the accessories delivered are complete. 

• 

Check that there are no scratch or breakage in external 
appearance (case, front panel, or terminal, etc). 

X-TIO-B-     -     

   / Y 

(1) (2) (3)  (4) (5)  (6) (7) 

(1) Type 

B: Extension type (14 terminals) 

(2) Input channel 1,  (3) Input channel 2 

K:  TC K 

J:  TC J 

 

T:  TC T 

S:  TC S 

R:  TC R 

A:  TC PL

 

N:  TC N 

E:  TC E 

W: TC W5Re/W26Re   

 

B:  TC B 

D:  RTD Pt100   

 

 

 

P:  RTD JPt100 

1:  0 to 10 mV DC   

2:  0 to 100 mV DC 

3:  0 to 1 V DC 

4:  0 to 5 V DC   

 

5:  0 to 10 V DC 

6:  1 to 5 V DC 

7:  0 to 20 mA DC   

8:  4 to 20 mA DC 

(4) Control output 1,  (5) Control output 2 

M:  Relay contact output   

V:  Voltage pulse output 0/12 V DC 

4:  0 to 5 V DC 

5  0 to 10 V DC 

6:  1 to 5 V DC 

7:  0 to 20 mA DC 

8:  4 to 20 mA DC 

(6) CT1 input,  (7) CT2 input 

N: None 

P: CTL-6-P-N 

S: CTL-12-S56-10L-N 

 
 
 

3. PARTS DESCRIPTION 

 

Terminal cover

Indication lamps 

Address setting

switch 

Terminal cover 

Joint connector 

(Right-side) 

Joint connector 

(Left-side) 

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

FAIL/RUN 
RX/TX 
EVENT1 
EVENT2 
EVENT3 
EVTNT4 

 

 

[Indication lamps] 

 

FAIL/RUN 
When normally: 

A green lamp turns on (RUN) 

When abnormally:  A red lamp turns on (FAIL) 

 

RX/TX 
During data send and receive:  A green lamp turns on 

 

EVENT 1 to 4 
Display various states by setting. 
During ON state:  A green lamp turns on 

Display contents 
Event 1 state, Event 2 state, Comprehensive event state,   
Output state, Control state, Executing segment state,   
Time signal state

 

 
 

4. COMMUNICATION SETTING 

Set communication setting before mounting and wiring of SRX.

 

4.1 Module Address Setting 

Set an address of module. For this setting, use a small blade 
screwdriver.

 

 

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

FAIL/RUN
RX/TX 
EVENT1
EVENT2
EVENT3
EVTNT4 

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

High-order digit 
setting 
(Set value 

×

 10)

Setting range: 0 to 99 
(Factory set value: 00)

Low-order digit 
setting 
(Set value 

×

 1) 

Address setting switch 

 

 

• 

For Modbus, the value obtained by adding “1” to 
the set address corresponds to the address used 
for the actual program.

 

• 

Set the module address such that it is different to 
the other addresses on the same line. Otherwise, 
problems or malfunction may result.

 

 
 

 

 

Accessories

 

Instruction Manual (IMS01N03-E3) ........................... 1 

*