7. SPECIFICATIONS
Inputs
Number of inputs:
2 points
Isolated between each channel:
Thermocouple input, Voltage (low) input
Not isolated between each channel:
RTD input, Voltage (high) input,
Current input
Input type:
Thermocouple:
K, J, T, S, R, E, B, N (JIS-C1602-1995)
PLII
(NBS)
W5Re/W26Re
(ASTM-E988-96)
RTD:
Pt100 (JIS-C1604-1997)
JPt100 (JIS-C1604-1989, Pt100 of
JIS-C1604-1981)
Voltage (low):
0 to 100 mV DC
Voltage (high):
0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC
Current:
0 to 20 mA DC, 4 to 20 mA DC
(Input impedance: 250
)
Sampling cycle:
500 ms
PV bias:
Input span to
Input span
CT input:
2 points
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
Outputs
Number of outputs:
2 points
(Isolated between input and output, and
between output and power supply)
Output type:
Relay contact:
250 V AC, 3 A (Resistive load)
1a
contact
Electrical life: 300,000 times or more
(Rated
load)
Voltage pulse:
0/12 V DC
(Load resistance 600
or more)
Current:
0 to 20 mA DC, 4 to 20 mA DC
(Load resistance 600
or less)
Voltage:
0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC
(Load resistance 1 k
or more)
Control action
Number of controls:
2 points
Control method:
Brilliant PID control
Reverse action or direct action is
selectable (Specify when ordering)
Heat/Cool control is selectable
(Specify when ordering)
Additional function:
Autotuning function
Events
Number of events:
2 points/channel
Event type:
Temperature event:
Deviation high, Deviation low,
Deviation high/low, Band,
Process high, Process low
Heater break alarm (HBA),
Control loop break alarm (LBA),
Burnout, Temperature rise completion
Heater break alarm (HBA) function
Number of HBA:
2 points
Setting range:
0.0 to 100.0 A (0.0 A: OFF)
Additional function:
Number of alarm delay times:
1 to 255 times
Control loop break alarm (LBA) function
Number of LBA:
2 points
LBA time:
1 to 7200 seconds
LBA deadband (LBD) setting:
0 to Input span
Optional
Event input
Number of inputs:
1 point
Input type:
Dry contact input
Input voltage:
24 V DC (Rated)
Input current:
Approx. 6 mA
Input details:
Control RUN/STOP,
Event interlock release
(Specify when ordering)
Event output
Number of outputs:
2 points
Output type:
Relay contact output
250 V AC, 1 A (Resistive load)
1a contact
Electrical life: 300,000 times or more
(Rated
load)
Output details:
Temperature event, Heater break alarm
(HBA), Control loop break alarm (LBA),
Burnout, Temperature rise completion
(Specify when ordering)
Communications
Communication interface:
Based on RS-485, EIA standard
Communication protocol:
CC-Link: Ver. 1.10/Ver. 2.00
Host
communication:
RKC
communication
(ANSI X3.28-1976 subcategories 2.5
and A4) or Modbus
General specifications
Power supply voltage: 21.6 to 26.4 V DC
(Including power supply voltage variation)
Rating: 24 V DC
Current consumption:
180 mA max./module
Allowable ambient temperature range:
10 to
50
C
Allowable ambient humidity range:
5 to 95 %RH (Non condensing)
Absolute humidity:
MAX.W.C 29 g/m
3
dry air at 101.3 kPa
Weight:
With event input/output:
Approx. 280 g
Without event input/output:
Approx. 270 g
Standard
Safety standard: UL:
UL61010-1
cUL: CAN/CSA-C22.2
No.61010-1
CE marking:
LVD: EN61010-1
OVERVOLTAGE
CATEGORYII,
POLLUTION DEGREE 2,
Class II (Reinforced insulation)
EMC: EN61326-1
C-Tick: EN55011