background image

 

®

RKC INSTRUMENT INC. 

 
The first edition: MAY 2015 [IMQ00]

HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN 

PHONE:  03-3751-9799 (+81 3 3751 9799) 

E-mail:  [email protected] 

FAX: 

03-3751-8585 (+81 3 3751 8585) 

Website:  http://www.rkcinst.com/ 

MAY 2015

Company names and product names used in this manual are the trademarks or registered
trademarks of the respective companies.

 

 

4. WIRING 

 
 
 
 
 
 

 

Wiring Cautions 

  To avoid noise induction, keep communication signal wire away 

from instrument power line, load lines and power lines of other 
electric equipment. 

 If the personal computer is easily affected by noise, use the 

ferrite core in the USB cable. For an installation position of a 
ferrite core, please refer to the following figure. 

 

Ferrite core * (sold separately) 

* Recommended ferrite core: 

ZCAT2032-0930 (TDK Corporation)

USB cable 

 

 

 

Method to connect 

(1) For loader communication 

 
 
 
 
 
 
 
 
 
 
 
 

 

W-BV-01 loader communication cable: 
It is possible to use COM-K2 when controller is either ON or 
OFF. COM-K2 starts supplying power to the connected 
controller being OFF after approximately 2 seconds.

 

W-BV-03 loader communication cable: 
Controller should be always ON to use with COM-K2. 

 

Display of controller (RKC product) being powered by COM-K2

FB series,   
RB series etc. 

Displays “-----” at the PV/SV monitor display.

PF900/901 

Lights all State monitor lamps: RESET, RUN, 
FIX, MAN, HOLD, STEP.SET and PTN.END. 
Other displays and lamps are OFF. 

 

(2) For RS-485/RS-422A communication 

 

The shielded twisted pair wire must be provided by the customer. 

 
 
 
 
 
 
 
 
 
 
 

 

Connector pin configuration 

 

1  2 3 4  5 

RS-485/RS-422A 

communication 

connector 

 

 

[RS-485] [RS-422A] 

Pin No.  Signal name 

Symbol 

 

Pin No.

 

Signal name Symbol

Signal ground 

SG 

 

Signal ground

SG 

Send data/ 

Receive data 

T/R (A)   

Send data 

T (A)

Send data/ 

Receive data 

T/R (B)   

Send data 

T (B)

4 * 

Unused 

 

 

Receive data

R (A)

5 * 

Unused 

 

 

Receive data

R (B)

* Do not connect wires to 4 and 5 pins. Malfunction may result. 

 

 

Connection diagram 

[RS-485] 

 
 
 
 
 
 
 
 
 
 

 

[RS-422A] 

 
 
 
 
 
 
 
 
 
 

 

* The termination resistor is built into the COM-K2. 

 

 

Attention in connector wiring 

  The lead wires use the stranded wire. 

  Use the stranded wire from size 0.25 to 0.5 mm

2

 (AWG 26-20). 

  Stripping length is as follows. 

 

8 mm (Stripping length) 

Conductor cross section: 

0.25 to 0.5 mm

2

 (AWG 26-20) 

Connector type:
 FK-MC 

0,5/5-ST-2,5 

  (Products by Phoenix
 contact 

Ltd.) 

 

 

Installation of USB device driver 

For installing the USB driver, refer to the following instruction manuals. 
The manuals can be downloaded from the official RKC website. 

  Installation of USB driver for COM-K2 communication converter (IMT01D13-E

 

USB Communication Converter COM-K2 USB Driver Installation Manual 
(IMT01D12-E

 

5. SPECIFICATIONS

 

USB function 

Interface: 

Based on USB Ver. 2.0 

Communication speed:  Full speed (12 Mbps) 
Connection: 

Connected by universal USB cable 
(Mini-B connector) 

Power source method:  Bus power (The power is supplied from the 

USB port on the personal computer side) 

Compatible OS: 

Windows XP */Windows Vista */Windows 7 * 
/Windows 8 */Windows 8.1 *   

*32-bit/64-bit 

 

Communication function 

Interface: 

Based on RS-485, EIA standard 

 

Based on RS-422A, EIA standard 

Connection method: 

2-wire system,   
half-duplex multi-drop connection (RS-485) 
4-wire system,   
half-duplex multi-drop connection (RS-422A) 

Synchronous method:  Half-duplex start-stop synchronous type 
Communication speed:  2400 bps, 4800 bps, 9600 bps, 19200 bps, 

38400 bps 

Data bit configuration:  Start bit:  1 

Data bit:  7 or 8 
Parity bit:  Without, Odd or Even 
Stop bit:  1 or 2 

Protocol: 

Protocol depends on application of the 
personal computer side 

Number of connecting controllers 
 

Maximum 31 controllers (RS-485, RS-422A) 

Termination resistor: 

Built-in termination resistor (120 

 

General specifications 

Power supply voltage:  5 V DC 

 (Supplied by USB bus cable) 

Current consumption:  150 mA max. (Loader communication) 

60 mA max. (RS-485/RS-422A communication) 

Allowable ambient temperature range:   

10 to 

50 

Allowable ambient humidity range:   

5 to 95 %RH (Non condensing) 
Absolute humidity:   
MAX.W.C 29.3 g/m

3

 dry air at 101.3 kPa 

Weight: 

Approx. 40 g (Instrument only)

 

 

   
   

To prevent electric shock or instrument failure, turn off the 
power before connecting or disconnecting the instrument 
and peripheral equipment.

 

!

 

WARNING 

RS-485/RS-422A 

Connected to USB 
port of a personal 
computer 

Connected to communication 

terminals of controller   

(Example: FB400/900) 

Connected to USB connector 

Connected to   

RS-485/RS-422A 

communication 

connector 

COM-K2

Shielded twisted pair wire 

USB cable 

Connected to loader communication connector 
of the controller (Example: FB400/900) 

Connected to USB 
port of a personal 
computer 

Connected to USB connector

Connected to loader 
communication 
connector 

Loader communication 
cable [Optional] 
W-BV-01 or W-BV-03 

USB cable 

COM-K2 

Shielded twisted   

pair wire 

Controller 

(Example: FB400/900) 

RS-485/RS-422A

communication 

connector 

Communication terminals

(Communication 1 side) 

R: Termination resistors (Example: 120 

 1/2 W) 

If communication errors occur frequently due to 
the operation environment or the communication 
distance, connect termination resistors. 

T/R (A)

T/R (B)

1

SG

2

R

COM-K2*

3

4

5

 

 

25  SG 

26 

27 

T/R (A)

T/R (B)

Shielded twisted   

pair wire 

Controller 

(Example: FB400/900)

RS-485/RS-422A 

communication 

connector 

Communication terminals 

(Communication 1 side) 

T (A)

R (A)

1

SG

2

COM-K2*

3

4

5

T (A)

R (A)

25 SG 

26 

27 

28 

29 

T (B)

R (B)

T (B)

R (B)

Reviews: