Riverside Hydronics EMX SERIES Installation & Maintenance Manual Download Page 10

EMX, EMXO and EMXGO SERIES WATER BOILERS 

34-503 07/13 

 

 

10

13 VENT TERMINATION 

CAUTION: Never size a flue vent based only on the flue outlet size of the product.

 

 

Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, Venting of 
Equipment, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the 
building codes. 

 

1.  A flue vent passing through the roof must be terminated in accordance with Section 7.6.2, Gas Vent 

Termination, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of 
the local building codes. 
 

2.  A gas vent passing through a wall must be terminated in accordance with Section 7.8, Through the Wall 

Vent Termination, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable 
provisions of the local building codes. 

 

WARNING: Vent connectors serving appliances vented by natural draft shall not be connected into 
any portion of mechanical draft systems operating under positive pressure

. Failure to observe this 

warning could result in property damage, serious injury or death.

 

 

3.  The vent connector must be the same size as the product flue outlet. The vent size must be determined 

by the BTU input of the product(s) and the vent design. The horizontal breeching of a vent must have at 
least 1/4" rise per linear foot not to exceed the length of horizontal vent. 

 

CAUTION: Do not weld or support breaching to product flue outlet. Adequate support of the venting 
system must be provided in compliance with local or other applicable codes. 
 
WARNING: The appliance must use only draft regulators as supplied by the appliance manufacturer 
for these purposes. Failure to use the correct draft regulators could result in carbon monoxide 
poisoning causing personal injury or loss of life. 

 

4.  Draft regulators (barometric dampers) may be incorporated in the vent for gas, oil, and gas/oil fan 

assisted products and are recommended. A single swing barometric damper should be used for oil-fired 
products. The double swing type should be used on gas or gas/oil fired products. Under normal venting 
conditions, the draft regulator should be the same size as the flue outlet of the product, never smaller. 
Draft regulators must be installed and adjusted in accordance with the manufacturer's instructions. 

 

IMPORTANT: 

A minimum of -.02" to -.06" W.C. draft is required for appliances vented by natural draft. 

 

 

Summary of Contents for EMX SERIES

Page 1: ...ation adjustment alteration service or maintenance can cause property damage personal injury exposure to hazardous materials or loss of life Refer to the information contained in this manual A qualifi...

Page 2: ...ipment Before You Install 4 Warranty 5 Codes 6 Location 7 Installation 8 Service Clearances 9 Clearances to Combustible Surfaces 10 Electrical 11 Venting 12 Combustion Ventilation Air Opening 13 Vent...

Page 3: ...neering controls Use NIOSH MSHA approved respirators as required see MSDS Wear long sleeved loose fitting clothing eye protection and gloves FIRST AID MEASURES If any of the irritations listed persist...

Page 4: ...OR THE PHYSICALLY HANDICAPPED HOSPITALS AND NURSING HOMES ELDER CARE FACILITIES AND REST HOMES ORPHANAGES AND CHILD CARE FACILITIES OTHER INSTALLATIONS WHERE RESPONSE TO CONTACT WITH HOT WATER MAY BE...

Page 5: ...ATURE AND PRESSURE GAUGES 8 3 HANDHOLE CLEANOUT 3 CONTROL ENCLOSURE 9 FLOAT LWCO Optional 4 GAS INLET 10 BOILER WATER RETURN 5 ASME PRESSURE RELIEF VALVE 11 BOILER WATER OUTLET 6 COMBINATION BOTTOM BL...

Page 6: ...iances conform to the latest edition of the ASME Boiler and Pressure Vessel Code Section IV Where required by the authority having jurisdiction the installation must comply with the Canadian Associati...

Page 7: ...ss for service is 18 at sides and rear and 24 in front 10 ELECTRICAL WARNING Turn off all electrical service to the appliance when accessing the controls located inside the control cabinet The cabinet...

Page 8: ...ING Vent this appliance in accordance with the latest edition of the National Fuel Gas Code and in accordance with the authority having jurisdiction See National Fuel Gas Code for complete requirement...

Page 9: ...2 each opening specified above should have a minimum free area of 1 square inch per 1 000 Btu h input CONFINED AREA FIGURE 1 Equipment located in confined spaces all air from outdoors CONFINED AREA F...

Page 10: ...y or death 3 The vent connector must be the same size as the product flue outlet The vent size must be determined by the BTU input of the product s and the vent design The horizontal breeching of a ve...

Page 11: ...uring and after operation Use care to avoid contact with skin while making adjustments 4 Conduct the following gas train leakage test before start up annual intervals and prior to investigating the ca...

Page 12: ...03 07 13 12 Record the following information for future use 1 Manifold gas pressure W C 2 Vent pressure W C 3 O2 reading 5 7 4 CO2 reading 8 9 5 CO reading ppm less than 300 ppm 6 NOx reading ppm 7 Ve...

Page 13: ...1850 3250 6700 125 1020 1650 2950 6000 150 950 1500 2650 5500 175 850 1370 2450 5000 200 800 1280 2280 4600 TABLE 1 Multiplier for Propane 1 57 Multiplier for alternate pressure drops 0 3 W C 0 77 1 0...

Page 14: ...f the pump The pump is a positive displacement type and pumps a constant volume of oil only a portion of which is used by the nozzle s the remainder being bypassed to the return line During gas operat...

Page 15: ...equipment operator Table 3 page 17 Since boiler designs vary only some of these listed inspections may be appropriate for your particular model Proper water treatment is critical to prevent corrosion...

Page 16: ...circuit to stop the burner at the proper point then SHUT DOWN THE BURNER IMMEDIATELY Do not restart until all cross connecting piping is checked for obstructions Also check the float bowl If these ar...

Page 17: ...INSPECTION REPORT DATE BURNER INSPECTION COMBUSTION ANALYSIS TANK INSPECTION TANK FLUSH CLEANOUT PRV TEST INSPECTION VENT INSPECTION THERMOSTAT INSPECTION GAS TRAIN LEAK TEST Recommended Inspection In...

Page 18: ...EMX EMXO and EMXGO SERIES WATER BOILERS 34 503 07 13 18 Riverside Hydronics LLC 990 Haltom Road Ft Worth TX 76117 1 800 990 5918 www riversidehydronics com...

Reviews: