3    

MOUNTING 

Mounting area between base plate and foundation must be flat and even. 
 
a)  Lower the voltage transformer onto foundation. 
b)  Compensate gap(s) - if any - between base plate and foundation. 
c)  Screw base rails of the voltage transformer with screws size M12 quality A2-70 (tensile 

strength 700 N/mm²) to the foundation. Prescribed tightening torque:  M = 30 Nm. 

4   

INSTALLATION CHECK INSTRUCTIONS 

a)  Is the cast resin body of the voltage transformer undamaged? 
b)  Are the metal parts undamaged? 
c)  Is  the  voltage  transformer  positioned  on  an  even  surface,  i.e.,  has  an  existing  gap 

between mounting base plate and foundation been compensated? 

d)  Has the prescribed torque „mounting base plate - foundation“ (see 3.c) been adhered 

to? 

 

Reviews: