background image

Hydro-Air Components, Inc., manufacturer of the 
Rittling product line, guarantees their products to 
be free from defects in material and workmanship 
for a period of one year from date of shipment 
from our Buffalo, New York factory.

Should there be any defects in the good(s), the 
purchaser should promptly notify Hydro-Air 
Components, Inc. and upon receipt of written 
consent from Hydro-Air Components, Inc., the 
purchaser shall return the defective good(s) to 
the factory for inspection with freight prepaid. If 
inspection shows the goods to be defective, 
Hydro-Air Components, Inc. will at its discretion 
repair or replace the said item(s).

Defects arising from damage due to shipment, 
improper installation, negligence or misuse by 
others are not covered by this warranty.

This warranty is extended only to the original 
purchaser from Hydro-Air Components, Inc.

WARRANTY

100 Rittling Blvd.  •  Buffalo, NY 14220
Phone: 716-827-6510  •  Fax: 716-827-6523  
Toll-Free: 800-FIN-TUBE (800-346-8823)
E-mail: [email protected]  •  www.Rittling.com   

 

     

     Revised 0209

(ANG BKT)

(FIN BKT)

PED-SM

The PED-SM floor post is typically used to mount 
PR or PRF radiators.  Also, PR2F and PR3F radiators 
over four tubes tall must also be mounted on PED-
SM  floor  posts.    The ANG  BKT  (PR  &  PR2F)  or 
FIN  BKT  (PRF  &  PR3F)  wall  mounting  brackets 
supplied  with  the  radiator  are  bolted  to  the  floor 
post, using nuts and bolts supplied by the installer.  
The leveling bolt screws into the radiator and rests 
against the floor post to level the radiator.

The  3”x3”  base  has  four  mounting  holes.    The 
installer supplies the appropriate mounting bolts to 
secure the PED-SM base to the floor.  

The PED-SM’s height is fixed to provide 3” clearance 
under the radiator, unless otherwise specified.

PED-BM-SQ

The PED-BM-SQ pedestal is used to mount PR2F or 
PR3F radiators, up to four tubes tall.  Radiators over 
four tubes tall should not be mounted on PED-BM-SQ 
pedestals, because they will be unstable.  Mounting 
is  accomplished  by  setting  the  radiator  down  over 
the fingers of the PED-BM-SQ.  The bottom tubes 
of the radiator rest on the pedestal, while the fingers 
protrude up through the fins to stabilize the radiator.

For Radiators  without Fins (on the back side of the 
panel) – no wall mounting clips should be ordered for 
radiators to be mounted on PED-BM-SQ pedestals.  
The  3”x3”  base  has  four  mounting  holes.    The 
installer supplies the appropriate mounting bolts to 
secure the PED-BM-SQ base to the floor.

The  PED-BM-SQ’s  height  is  fixed  to  provide  3” 
clearance  under  the  radiator,  unless  otherwise 
specified.

FIN BKT

ANG BKT

PED-BM-SQ

PED-SM

(PED-BM-SQ)

(PED-SM)

(PR-CLIP)

PR CLIP

Summary of Contents for PR1

Page 1: ... or pipe dope used is the installer s choice make sure the connections are leak tight One quarter of a turn past hand tight is usually sufficient Each radiator needs to be fitted with a 1 8 air vent prior to startup Installation Instructions Radiators are boxed together in as few crates as 1 possible A box of brackets is included as a separate piece and it is marked to denote brackets Inside the c...

Page 2: ...curely fastened to the floor using appropriate fasteners Radiators sit on the pedestals with the fingers of the pedestals sticking up between the fins to provide stability Radiators expand a maximum of 0 016 inch per linear 4 foot of length if heated to 215º F Piping attached to the radiator must provide the necessary expansion compensation When the system has been shown to hold 50 psi 5 maximum a...

Page 3: ...ng whether operated by a simple thermostat to baseboard loop system or an advanced boiler reset controller with motorized mixing valves constant circulation and two pipe distribution Radiator Maintenance Hydronic System Maintenance should include routine 1 checks for piping leaks usually indicated by frequent makeup water and a yearly diagnosis of the system water pH to evaluate its corrosive pote...

Page 4: ...d on PED SM floor posts The ANG BKT PR PR2F or FIN BKT PRF PR3F wall mounting brackets supplied with the radiator are bolted to the floor post using nuts and bolts supplied by the installer The leveling bolt screws into the radiator and rests against the floor post to level the radiator The 3 x3 base has four mounting holes The installer supplies the appropriate mounting bolts to secure the PED SM...