10.6.3
Timeouts
● Browsing [20 s]*: Switches back from the display of older messages to the basic
message display state.
● Menu [30 s]*: Returns to the basic state from the operating menu.
● Display [40 s]*: Returns from a function display to the menu.
● Program [1800 s]*: Returns from a programming function to the menu.
● Message [15 s]*: Duration of the event display for a menu function.
● Code [15 s]*: Timeout for menu functions without their own timeout.
● Edit [60 s]*: Exits input mode.
● Test [1800 s]*: Exits the display mode of a diagnostics function (air flow display,
air flow calibration, alarm device (AD) calibration, battery status indicator, tem-
perature indicator).
● Battery failure is only displayed after 60 seconds*.
● Power supply failure is displayed after 60 seconds*.
● Maintenance is displayed after a maximum of 730 days*.
● Battery change is displayed after 730 days*.
● Air flow monitoring filter time: This fault is only displayed after 120 seconds*.
● Extinguishing delay: Extinguishing is delayed by 0 seconds*.
The delay time can be set to a maximum of 120 seconds.
When configuring the setting, observe the applicable provisions, guidelines, and
laws at the location.
* Factory setting
10.6.4
Threshold values
● Air flow monitoring lower threshold: the lower value of the air flow calibration is
displayed.
● Air flow monitoring upper threshold: the upper value of the air flow calibration is
displayed.
● AE (alarm device) monitoring lower threshold: the lower value of the alarm
device is displayed (wire break/short circuit monitoring).
● AE (alarm device) monitoring upper threshold: the upper value of the alarm
device is displayed (wire break/short circuit monitoring).
● Extinguishing agent monitoring filter time: Setting for the delay in minutes until
display of the extinguishing agent leak.
● Temperature MIN [°C]: Setting for the lowest operating temperature (restricted by
the manufacturer to 10 °C (50 °F)).
● Temperature MAX [°C]: Setting for the highest operating temperature (restricted
by the manufacturer to 40 °C (104 °F)).