24
F 1 Check list –
Commencing operation of CMC-TC Master
DK 7320.000
Com Port
Com
1
2
3
4
5
Note:
Prior to installation and commencing operation the installation
and operating instructions, including the safety advice, (see
1. Safety
advice
) must be read and observed.
The operating instructions are included as a two-language version
(German/ English) as a PDF file together with a current Adobe
Acrobat reader version on the enclosed CD-ROM.
German:
A29669_xx_IT74_G.pdf
English:
A29669_xx_IT74_E.pdf
Assembly:
Prior to installation the installing technician must check
the completeness of the scope of supply (see Appendix
A Scope of
supply/Accessories
) including the required accessories.
Further to that, the installer must make sure that the system complies
with the admissible conditions of use, particularly the admissible
ambient temperatures and the required IP protection category, see
Appendix
B Technical data
.
See also Appendix D Installation instructions
Configuration of CMC-TC Master at commencement of
operation
: (see
Appendix E Configuration of serial interface
RS 232
) Start terminal program, e.g. Hyperterminal – Part of
MS Windows
1.
Query User name:
cmc
(Factory setting)
Password:
cmc
(Factory setting)
2.
Select menu item:
1
Network configuration
1
IP configuration
3.
Entering/Changing IP Addresses
1. IP Address: 192.168.30.100
(Factory setting)
2. IP Subnet mask: 255.255.255.0
(Factory setting)
3. IP Router xxx.xxx.xxx.xxx
Confirm:
ENTER
, Store: “
Activate values
”
Call browser:
1. Select the browser as usual
2.
Enter at http prompt the IP address entered in point 4 of the
RITTAL CMC-TC Master:
e.g.:
http://192.168.30.100
The security notes must be confirmed.
The login window opens, enter user name and password.
Factory setting:
rittal
and
rittal
.
Factory setting – Supervisor:
admin
and
admin
.
3. The browser window of the Master, shown on left, opens.
Electrical connection:
Note:
It is indispensable to observe the information given in 4.2
Electrical Components and in
Appendix E 1 Electrical connection –
CMC-TC Master
.
1.
Plug in Ethernet network connection by RJ 45 connector.
2.
Make connection between Master and PU.
3.
Connect consoles (Monitor, keyboard and mouse) optional.
4.
Connect alarm relay.
5.
Plug in IEC connection cable / earthing of rear panel.
Rittal
CMC-TC