5 Assembly and siting
EN
26
Rittal Liquid Cooling Package
the baying connectors into alignment with the at-
tachment points.
Attaching the LCP Inline
Before baying the LCP Inline, dismantle any parti-
tions or side panels that may be present on the serv-
er enclosure.
In the front section, push out a baying clamp
(fig. 27, item 3) from the server enclosure (fig. 27,
item 2) through the corresponding notch in the side
panel of the LCP Inline (fig. 27, item 1).
From the server enclosure, tighten the baying clamp
(fig. 27, item 4), so that the frames of the server en-
closure and LCP Inline are firmly connected to one
another.
Fig. 27:
Baying clamp
Key
1
LCP Inline
2
Server enclosure
3
Baying clamp
4
Assembly screw of baying clamp
In the same way, insert a second baying clamp to
connect the server enclosure and LCP Inline in the
rear section.
All device versions:
Where applicable, attach the rear door to the LCP
Rack or to the rear adaptor of the LCP Inline.
Finally, check the stability of the Liquid Cooling
Package once again.
5.2.8
Mounting the side panel
If the Liquid Cooling Package is not bayed between
two server enclosures, close it off with a side panel.
Proceed as follows to assemble the side panel:
Remove the various assembly components from the
optional side panel package (Model. No. 8100.235)
or use those from a server enclosure which has al-
ready been dismantled.
Using the assembly screws, mount the assembly
components (2 side panel mountings, 2 side panel
mounting brackets, 6 side panel holders) onto the
side of the Liquid Cooling Package which is oppo-
site to the server enclosure.
Place both side panel mountings as symmetrically
as possible onto the upper mounting rail of the
Liquid Cooling Package and, using your hand,
press them firmly in place.
Screw down the two side panel mounting brackets
top and bottom in the centre of the mounting rail us-
ing one screw each.
Screw down 3 side panel holders onto each of the
two side mounting rails with one screw each.
Mount a side panel onto the two side panel mount-
ings of the Liquid Cooling Package and align them
to the front and rear of the unit.
Using the 8 assembly screws, screw the side panel
firmly onto the side panel holders and the side panel
mounting brackets.
5.3
Fan installation
As delivered, the Liquid Cooling Package contains the
following number of fan modules as standard:
LCP Rack and LCP Inline:
– 30 kW version (3311.138/238/538):
One fan module at position 3
– 60 kW version (3311.268/568):
Four fan modules at positions 2, 3, 4 and 5
LCP Inline flush:
– 30 kW version (3311.148/548):
Two fan modules at positions 1 and 3
Depending on the required cooling output and in or-
der to form redundancies, up to a maximum of six fan
Note:
If the rear frame is fitted on the LCP Inline, it
may alternatively be fitted at the
rear
be-
tween the frame and the server enclosure,
analogous to the LCP Rack, using three bay-
ing clamps (see the section on "Attaching
the LCP Rack").
1
3
4
2
Caution! Risk of injury!
The side panel holders have sharp-edged
teeth, to enable earthing of the side panel
through the Liquid Cooling Package.
Note:
The maximum of four fans in the LCP Inline
flush are located in positions 1, 2, 3 and 4.
Please take particular note of this when con-
necting the fans (see section 5.3 "Fan instal-
lation").