Rittal Liquid Cooling Package
MinValvPosition
0
50
This setting guarantees a mini-
mum flow at all times, whereby the
control system is able to react
more spontaneously to sudden
capacity increases.
Analogous to the minimum fan speed (pa-
rameter "RegParMinDrz"), permanent
opening of the control valve for all operat-
ing modes may be set here.
"Automatic" operating mode
The control valve is always opened at least
to the value set here. Exception: In case of
leaks, if the "0" setting is selected (= Emer-
gency), the valve is closed completely
(see parameter "LeakageMode").
"Minimum" operating mode
The control valve is always opened at least
to the value set here.
"Manual" operating mode
If the operator enters an opening value for
the control valve which is less than the
minimum opening set here, the value is
automatically corrected to the minimum
opening.
DtMin
0
20
The fans operate at the lowest fan
speed beneath this temperature
difference (see parameter "Reg-
ParMinDrz").
Linear fan control occurs in the range be-
tween DtMin and DtMax.
DtMax
3
40
The fans operate at the highest fan
speed above this temperature dif-
ference (100%).
SensorType
0
1
Reserve option. Currently no settings that
affect the system.
SensorRate
0
1
Reserve option. Currently no settings that
affect the system.
FlowCorPar1
Correction factor for water sensors for inlet
and return (Grundfos).
FlowCorPar2
Correction factor for water sensors for inlet
and return (Grundfos).
Designation
Min
Max
Definition
Description